Inspection ID Issue Date Code Violation Description Has Red Tag Has Re Inspection
MERM-8DPRRM 1/13/2011 1.18 Car door restrictor shall be operational.
MERM-8DPRRM 1/13/2011 F2 final limit needs to be operational.
MERM-8DPRRM 1/13/2011 S1 Main floor recall devices need to re-call elevators to main floor. 60 day re-inspection required.
MERM-83MSFG 3/12/2010 B3 Car top emergency exit must be accessible without the use of special tools.
MERM-83MSFG 3/12/2010 H2 Roof drain line over #1 controller must be guttered / guarded to prevent leakage onto equipment.