MERM-8H94ZG
|
5/10/2011
|
1.5
|
The emergency light fixture inside the elevator is not operational and shall be repaired.
|
|
|
MERM-9743MU
|
4/19/2013
|
11 CSR 40-5.090 3.A
|
The testing has not been completed on the elevator at this time. The weight test needs to be performed, safeties set and fireman?s service testing before the inspection is completed.
|
|
|
MERM-8H94ZG
|
5/10/2011
|
11 CSR 40-5.100
|
The current state operating certificate needs to be posted in the machine room in a non combustible frame.
|
|
|
MERM-9J63Z6
|
4/7/2014
|
2.41
|
8.6.1.4 There shall be maintenance records kept in the elevator machine room or accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams.
|
|
|
MERM-8US489
|
5/9/2012
|
A17.2 2.6
|
The ventilation fan in the dispatch/emergency power cabinet needs to be repaired to provide proper operation temperature.
|
|
|