Inspection ID | Issue Date | Code | Violation Description | Has Red Tag | Has Re Inspection |
---|---|---|---|---|---|
5/15/2006 | 1001.2a8 | ||||
5/25/2004 | 1200.6a | ||||
MERM-9J63Z6 | 4/7/2014 | 2.41 | 8.6.1.4 There shall be maintenance records kept in the elevator machine room or accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. | ||
MERP-7GQULG | 6/13/2008 | 5.2 | Counterweight runby must be at a minimum of 6". Counterweight runby is currently 1" and now requires the hoistway ropes to be shortened to comply with code. | ||
MERM-745SH4 | 5/14/2007 | 1001.2 (a) (8) | Door closing force greater than 30 fp, reduce force. |