Inspection
Inspection Details
Equipment ID
2119
2119
Inspection Date
12/2/2022
12/2/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Michael Bailey
Michael Bailey
Mechanic Name
Ross Colligan
Ross Colligan
Relief Valve Pressure
Slide
4
4
Governor Rope Pull
450
450
Door Closing Force
20
20
External ID
f8282534-3afb-4331-af22-6ece4f555b0d
f8282534-3afb-4331-af22-6ece4f555b0d
Location
Authenrieth Properties
2 N Meramec Ave, Clayton, MO
Phone: (314) 725-2414
2 N Meramec Ave, Clayton, MO
Phone: (314) 725-2414
Owner
Attn: Authenrieth Properties
Authenrieth Properties
#2 MERAMEC AVE, CLAYTON, MO 63105
Phone: (314) 725-2414
Email: Marjorie@schlaflycorporation.com
Authenrieth Properties
#2 MERAMEC AVE, CLAYTON, MO 63105
Phone: (314) 725-2414
Email: Marjorie@schlaflycorporation.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Remove standing water from the elevator pit | 12/31/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Repair inoperative emergency phone | 8/9/2018 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept clean of dirt and water. | 12/31/2018 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Tail sheave needs to be replaced due to water damage. | 12/31/2018 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self closing and self locking. | 12/31/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - n/a | n/a | No | No | Water in pit needs to be removed | 12/26/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.6 - Governor-rope tension devices | 8.11.2.1.5(g) | No | No | Governor tension sheave shall be replaced. 1" rod holding sheave is rusted out. | 12/26/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.9 - Buffers and emergency terminal speed limiting devices | 8.11.2.1.5(c) | No | No | Check integrity of pit buffers. | 12/26/2019 |
| MO Minimum : Elevators | (N) - Guide Rails | (N)2 | No | No | Check integrity of all rail bottoms (under water and large amounts of rust flaking off). 5.13 | 12/26/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 2.7.3.4 | No | No | Machine room door shall be self closing and locking, and steps leading up to room shall be attached. | 12/26/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Steps leading up to room shall be attached. | 12/25/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room door shall be self-closing and self-locking. | 12/25/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Machine room access door needs repair, door hinges pulled from frame and door. | 12/25/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test incomplete - Governor must be tested for electrical and jaw speeds. Re-inspection required | 12/2/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Elevator pit shall be kept dry and clean from all water or debris. Remove all water from elevator pit. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current state operating certificate shall be displayed inside of the elevator machine room. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A valid fire extinguisher shall be kept inside of the elevator machine room. |