Inspection
Inspection Details
Equipment ID
26030
26030
Inspection Date
11/30/2022
11/30/2022
Inspection Type
New Installation
New Installation
Inspector Name
Vincent Daus
Vincent Daus
Mechanic Name
Bobby Strader
Bobby Strader
Relief Valve Pressure
Slide
10"
10"
Governor Rope Pull
100/400
100/400
Door Closing Force
NA
NA
External ID
acb84794-8df9-4c74-93aa-5e0ef07c72bd
acb84794-8df9-4c74-93aa-5e0ef07c72bd
Location
21c Museum Hotel
1528 Locust St, St. Louis, MO
Phone: (314) 781-8000
1528 Locust St, St. Louis, MO
Phone: (314) 781-8000
Owner
Attn: Locust Street Property 1 STL, LLC
Locust Street Property 1 STL, LLC
1528 Locust St, St. Louis, MO 63103
Phone: (314) 781-8000
Email: boverbaugh@russellco.com
Locust Street Property 1 STL, LLC
1528 Locust St, St. Louis, MO 63103
Phone: (314) 781-8000
Email: boverbaugh@russellco.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.4 - Machine space | 2.8.1 | Yes | No | Pipe in machine room; remove or enclose. | 5/25/2023 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | Yes | No | 2.8.3.1.2 - Pipes (PVC and black iron) located at the top of the hoistway shall be removed or enclose hoistway with the proper fire rating material. | 5/25/2023 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | 2.1.1.2.2 - The 4 x 4 access hatchway at the top of the hoistway shall be enclosed or receive approval from the State of Missouri Compliance Inspection Manager. | 5/25/2023 |
| A17.1-2016 : Elevators | 3.13 - Windows, projections, recesses, and setbacks | 2.1.6 | Yes | No | 2.1.6.2 - Bevel all ledges in the hoistway at an angle not less than 75 degrees. | 5/25/2023 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | 2.1.1.2.2 - Enclose hole in the hoistway between lower level and the lobby. | 5/25/2023 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | Yes | No | 2.8.3.4 - Pipe in the pit at the back wall, right side shall be removed or enclosed. | 5/25/2023 |
| A17.1-2016 : Elevators | 3.12 - Pipes, wiring, and ducts | 2.8 | Yes | No | 2.8.3.4 - Pipe in the pit at the back wall, left side shall be removed or enclosed. | 5/25/2023 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 2.1 | Yes | No | 2.1.1.2.2 & 2.1.6.2 - Enclose the wall behind the counterweight guard and bevel edge. | 5/25/2023 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.8 | Yes | No | 2.8.2.2 - Remove the non elevator switches at the rear of the pit and enclose. | 5/25/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.10 Acceptance Inspection and Test | Yes | No | The violations from this inspection were discovered during the temporary use inspection. Additional violations may be cited before the final acceptance. | 5/25/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 12/4/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Unintended motion in the up direction needs to be tested. | 4/28/2026 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.10.2.2.2(l) | No | No | Machine room shall have proper fire extinguisher and shall have current monthly/annual test tag. | 4/28/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Fire service testing must be documented monthly, the form is present in the MCP, but hass not been logged monthly. | 4/28/2026 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current MO State operating certificate shall be displayed in the equipment room in a non-combustible frame. | 4/28/2026 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit shall be kep clean. Remove excess dabris. | 4/28/2026 |
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | No | No | Fire service testing must be documented monthly, the form is present in the MCP, but hass not been logged monthly. | |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current MO State operating certificate shall be displayed in the equipment room in a non-combustible frame. | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Pit shall be kep clean. Remove excess dabris. | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | Yes | No | Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually. |