Inspection
Inspection Details
Equipment ID
15265
15265
Inspection Date
12/7/2022
12/7/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Walter Tauchert
Walter Tauchert
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
20
20
External ID
6e2b5813-0771-45cf-a95d-f27c5d12e1e2
6e2b5813-0771-45cf-a95d-f27c5d12e1e2
Location
Jefferson County Courthouse
300 Main St, Hillsboro, MO
Phone: (636) 797-5314
Alt Phone: (314) 775-6457
Fax: (636) 797-6390
300 Main St, Hillsboro, MO
Phone: (636) 797-5314
Alt Phone: (314) 775-6457
Fax: (636) 797-6390
Owner
Attn: Jefferson County
Jefferson County
PO Box 100, Hillsboro, MO 63050
Phone: (000) 000-0000
Email: MRusso@jeffcomo.org
Jefferson County
PO Box 100, Hillsboro, MO 63050
Phone: (000) 000-0000
Email: MRusso@jeffcomo.org
Billing
Attn: Jefferson County
Jefferson County
300 Main St, Hillsboro, MO 63050
Phone: (636) 797-5340
Email: MStinchcomb@jeffcomo.org
Jefferson County
300 Main St, Hillsboro, MO 63050
Phone: (636) 797-5340
Email: MStinchcomb@jeffcomo.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Emergency light shall work. | 4/16/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | Emergency alarm bell shall work. | 4/16/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | One suspension rope is missing a shackle end cable clip. | 11/23/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Provide on-site maintenance control program. | 11/23/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Maintenance records shall be kept on site. | 8/10/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in car works, but dials 911. Reprogram to call non emergency number with 24/7 support. | 11/20/2023 |
| A17.1-2016 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.4.11 Runby (Re-Inspect) | Yes | No | Counterweights strike buffer with car at top floor, minimum runby is less than 6". Hoist ropes need to be shortened to attain 6-12" measurement | 12/14/2023 |
| MO Minimum : Elevators | (A) - Hoistways | (A)9 | No | No | Provide key(s) for emergency stop switch in car | 6/13/2024 |
| MO Minimum : Elevators | (A) - Hoistways | (A)9 | No | No | Provide keys for emergency stop switch in car | 6/13/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Inspection is incomplete due to the elevator being stuck on the safeties. The following items still need to be tested: Governor pull out/thru, governor switch/jaw, slide, unintended up, door pressure, phone, alarm, emergency light & fire service. | 5/5/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | Yes | Unit was red tagged due to severe rusting of the counterweight buffer and channel, rail clips at the bottom of the car and counterweights rails, and the brackets/feet for all four rails. | 2/9/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | None of the annual inspection was done due to red tag and shall be completed. RM | 2/9/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Complete annual inspection still needed. | 3/24/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | No | Car Buffer support channels appear severely damaged by rust. Replacement of these C-Channels is required or provide engineer stamped documentation of integrity | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Hoist Ropes appear dry and showing “rouge”. Ropes shall be cleaned and lubricated per OEM recommendations. |