Inspection
Inspection Details
Equipment ID
12426
12426
Inspection Date
9/11/2018
9/11/2018
Inspection Type
Reinspection
Reinspection
Inspector Name
Kurt Zimmerman
Kurt Zimmerman
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
fb746d54-e65d-4337-a357-1fc2882f2760
fb746d54-e65d-4337-a357-1fc2882f2760
Location
Construction Career Center
1224 GRATTAN ST, SAINT LOUIS, MO
1224 GRATTAN ST, SAINT LOUIS, MO
Owner
Attn: UNK
St. Louis College Prep
1224 GRATTAN ST, SAINT LOUIS, MO 63104
Phone: (000) 000-0000
St. Louis College Prep
1224 GRATTAN ST, SAINT LOUIS, MO 63104
Phone: (000) 000-0000
Billing
Attn: Mike Maoone
St. Louis College Prep
1224 GRATTAN ST, SAINT LOUIS, MO 63104
Phone: (314) 337-8982
Email: saintlouiscollegeprep@bill.com
St. Louis College Prep
1224 GRATTAN ST, SAINT LOUIS, MO 63104
Phone: (314) 337-8982
Email: saintlouiscollegeprep@bill.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | Repair drop ceiling or protect light bulb in fixtures | 8/24/2018 | ||
| conversion | conversion | n/a | Excessive leaking on cylinder packings | 8/24/2018 | ||
| conversion | conversion | n/a | Phone shall work | 8/24/2018 | ||
| conversion | conversion | n/a | car top shall be kept clean | 8/24/2018 | ||
| conversion | conversion | n/a | Pit shall be clean and dry | 8/24/2018 | ||
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Phone in elevator cab does not work. | 9/11/2018 | |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 11/6/2020 | |
| A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 9/28/2023 | ||
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | The pit lighting shall be increased. The lighting shall provide an illumination of not less than 10 foot-candles at the pit floor and at a pit platform, when provided. | 7/20/2022 | ||
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7 | Missing light covers in the car. | |||
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | 204.1b - Missing ceiling tiles in the car. | |||
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | Water and oil shall not be allowed to accumulate on the pit floor. | |||
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | |||
| A17.1-1996 : Elevators | 1.12 - Car enclosure | 204 | Repair drop ceiling or protect light bulb in fixtures. Cited multiple years. Ceiling grid does not properly secure tiles. Lamps shall have protective clear tubes to prevent broken glass from falling onto passengers. | |||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | Jack drain tubes, from wiper ring, shall be routed to measurable container in pit, not to exceed 5 gallons per jack. See State Memorandum 006. | |||
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | Pit FAID device (Smoke/heat detector) is damaged. Repair/replace as need. |