Inspection
Inspection Details
Equipment ID
14676
14676
Inspection Date
11/18/2022
11/18/2022
Inspection Type
Major Alteration
Major Alteration
Inspector Name
Daniel Letcher
Daniel Letcher
Mechanic Name
Terry Hodges
Terry Hodges
Relief Valve Pressure
450
450
Slide
Governor Rope Pull
Door Closing Force
14
14
External ID
b2afd49a-9f52-45a5-8d92-b5e093d6f8da
b2afd49a-9f52-45a5-8d92-b5e093d6f8da
Location
Bates County Memorial Hospital
615 W Nursery St, Butler, MO
Phone: (660) 679-4135
615 W Nursery St, Butler, MO
Phone: (660) 679-4135
Owner
Attn: Mike Keiser
Bates County Memorial Hospital
615 W Nursery St, Butler, MO 64730
Phone: (660) 200-7068
Email: mkeiser@bcmhospital.com
Bates County Memorial Hospital
615 W Nursery St, Butler, MO 64730
Phone: (660) 200-7068
Email: mkeiser@bcmhospital.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | replace the emergency light battery, it is dead | 7/31/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | machine room lights were not working | 10/3/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | the pit was full of water, maintain dry pit | 10/3/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | No | could not perform annual inspection because of water in pit and machine room lights not working | 11/24/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | No | No | the maintenance control program is missing the instructions for code checkout procedures | 10/3/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.10 replacement of Hydraulic jack,Plunger,Cylinder,Tanks,and Anticreep Leveling Device | Yes | Yes | elevator fail the set test, could not figure out where the oil was going. unit was red tagged | 11/18/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Replace burnt out cab ceiling lights, illumination inside the car does not meet the minimum requirements | 10/3/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Do not store non-Elevator related items in the machine room | 10/3/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Water in the pit, provide means to prevent the accumulation of ground water in the pit | 10/3/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Foam pad on tank lid is decomposing and dropping into the tank, clean or replace the oil | 10/3/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Missing pickup roller on the bottom landing hoistway door | 10/3/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | No | Water in the pit, provide means to prevent the accumulation of ground water in the pit - repeat violation, now requires reinspection | 1/17/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Replace missing ceiling tiles in the machine room | 1/17/2026 |