Inspection
Inspection Details
Equipment ID
8214
8214
Inspection Date
12/19/2022
12/19/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas Krug
Thomas Krug
Mechanic Name
Richard Toeniskoetter
Richard Toeniskoetter
Relief Valve Pressure
390
390
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
b1fe4c10-9dc4-46e9-a622-19727e6ba199
b1fe4c10-9dc4-46e9-a622-19727e6ba199
Location
St. Charles County Justice Center
301 N 2ND ST, SAINT CHARLES, MO
Phone: (636) 949-1810
301 N 2ND ST, SAINT CHARLES, MO
Phone: (636) 949-1810
Owner
Attn: St. Charles County Government
St. Charles County Government
300 N 2ND ST RM 101, SAINT CHARLES, MO 63301
Phone: (000) 000-0000
Email: cwterbrock@sccmo.org
St. Charles County Government
300 N 2ND ST RM 101, SAINT CHARLES, MO 63301
Phone: (000) 000-0000
Email: cwterbrock@sccmo.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4.1 | x | Verify main and lighting fuses for proper rating and face out. | 7/12/2025 | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | x | All FAID shall be tested. | 7/12/2025 | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.11.1.3 Emergency Phone not workng Alarm Functioning ( Mandatory Re-Inspection due in 14 days) | x | Remove phone button/communication loss panel @ 2. | 7/12/2025 | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Emergency power shall be tested. | 7/12/2025 | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | x | Machine room shall have at least 1 GFCI. | 7/12/2025 | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | x | Machine room lighting shall work and shall be at least 19fc. | 7/12/2025 | |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.9 | x | Install proper MOD/Alteration data tag. | 7/12/2025 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | x | Label all interface cabinets with description of operation in the machine room. | 7/12/2025 | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1.1.6 Verification of Telephone Operability | x | Remove phone button/communication loss panel @ 2. (To be re-inspected at completion of MOD on SID 8215) | 10/7/2025 | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | x | Emergency power shall be tested. (To be re-inspected at completion of MOD on SID 8215) | 10/7/2025 | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | x | Machine room shall have at least 1 GFCI. (To be re-inspected at completion of MOD on SID 8215) | 10/7/2025 | |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | x | Machine room lighting shall work and shall be at least 19fc. (To be re-inspected at completion of MOD on SID 8215) | 10/7/2025 | |
| A17.1-2016 : Elevators | 2.14 - Code data plate | 8.9 | x | Install proper MOD/Alteration data tag. (To be re-inspected at completion of MOD on SID 8215) | 10/7/2025 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | x | Label all interface cabinets with description of operation in the machine room. (To be re-inspected at completion of MOD on SID 8215) | 10/7/2025 |