Inspection
Inspection Details
Equipment ID
13325
13325
Inspection Date
12/13/2022
12/13/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Paul Karrenbrock
Paul Karrenbrock
Mechanic Name
Relief Valve Pressure
na
na
Slide
Governor Rope Pull
Door Closing Force
na
na
External ID
d3e2bb2a-83fd-4ebd-a124-2b2cb896270d
d3e2bb2a-83fd-4ebd-a124-2b2cb896270d
Location
Residence Inn
3290 Rider Trl S, Earth City, MO
Phone: (314) 209-0995
Email: kevin.gerschefske@marriott.com
3290 Rider Trl S, Earth City, MO
Phone: (314) 209-0995
Email: kevin.gerschefske@marriott.com
Owner
Attn: Equishotels LLC
Equishotels LLC
4220 Duncan Ave, Ste 201, St. Louis, MO 63110
Phone: (314) 932-3209
Email: donotreply@marriott.com
Equishotels LLC
4220 Duncan Ave, Ste 201, St. Louis, MO 63110
Phone: (314) 932-3209
Email: donotreply@marriott.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 2.35 - Supply Line and Shutoff Valve | 303 | No | No | A hydraulic fitting in the machine room is leaking excessively and shall be repaired. | 6/9/2020 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. | 6/9/2020 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 1001.2(d)12 | Yes | No | The fireman's emergency service phase I and II operations could not be tested. The elevator door operator was malfunctioning and the maintenance provider placed the unit out of service. | 11/20/2019 |
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV needs to be tested on or before next annual inspection. | 12/12/2022 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | No fire service instructions next to key switch inside elevator cab | 7/9/2024 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 7/9/2024 |
| A17.1-1996 : Elevators | 2.4 - Machine space | 101.2 | No | No | Remove non elevator related materials from machine room | 7/9/2024 |
| MO Minimum : Elevators | 2.3 - Lighting and receptacles | 110.27 Guarding of Live Parts NFPA 72 | No | No | Repair lights in machine room, wires are exposed. One light is out and fixture or bulbs need to be guarded | 7/9/2024 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | No fire service instructions next to key switch inside elevator cab. Re-inspection required | 7/9/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication inoperable. Re-inspection required | 4/26/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit needs to be cleaned | 7/9/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Cartop needs to be cleaned | 7/9/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Maintenance control program records need to be updated, including monthly fire service checks | 7/9/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | No fire service instructions next to key switch inside elevator cab | 7/9/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Unit not working properly at the time of inspection. | 6/16/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Valve leaking Oil back into tank. Repair or replace as needed. | 8/31/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | State operating certificate shall be displayed in elevator machine room. | 8/31/2025 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency communication inoperable. Phone line has no power, needs repaired. Re-inspection required | |
| A17.1-2016 : Elevators | 1.15 - sign and operating device symbols | 8.6.1.6.7 | No | No | Sign for Phase II instructions is illegible in side car, need to replace with new signage | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Valve leaking oil back into tank, repair or replace as needed |