Inspection
Inspection Details
Equipment ID
3202
3202
Inspection Date
12/16/2022
12/16/2022
Inspection Type
Major Alteration
Major Alteration
Inspector Name
David Folkert
David Folkert
Mechanic Name
Chad Davis
Chad Davis
Relief Valve Pressure
520
520
Slide
Governor Rope Pull
Door Closing Force
25
25
External ID
eab34ee2-b035-4dd5-bb6e-6d2c9ec69638
eab34ee2-b035-4dd5-bb6e-6d2c9ec69638
Location
Drury inn & Suites St. Joseph
4213 Frederick Ave, St. Joseph, MO
Phone: (816) 364-4700
4213 Frederick Ave, St. Joseph, MO
Phone: (816) 364-4700
Owner
Attn: Drury Southwest, Inc.
Drury Southwest, Inc.
101 S Farrar Dr, Cape Girardeau, MO 63701
Phone: (314) 587-3129
Email: Pat.Travers@druryhotels.com
Drury Southwest, Inc.
101 S Farrar Dr, Cape Girardeau, MO 63701
Phone: (314) 587-3129
Email: Pat.Travers@druryhotels.com
Billing
Attn: Drury inn & Suites St. Joseph
Drury inn & Suites St. Joseph
4213 Frederick Blvd, St. Joseph, MO 64506
Phone: (314) 587-3129
Email: p0024@druryhotels.com
Drury inn & Suites St. Joseph
4213 Frederick Blvd, St. Joseph, MO 64506
Phone: (314) 587-3129
Email: p0024@druryhotels.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Emergency alarm bell does not function. | 7/30/2018 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Hydraulic oil on machine room floor due to leaking control valve. | 4/4/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit floor has oil accumalation. Oil source is from leak in machine room. | 4/4/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Need to remove standing hydrauluc oil from elevator pit. Pits need to be kept clean and dry. | 5/6/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Post firefighter operating instructions next to hall fire keyswitch | 4/29/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Remove scavenger pump from pit. Cylinder drain line needs to drain into pit collection container of no more than 5 gallon capacity | 4/29/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | Yes | No | No visual signal during fire recall operation | 4/12/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Test and log firefighter operation monthly | 4/29/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.7 Firefighters Operations/Signage | No | No | Post firefighter operating instructions next to hall fire keyswitch | 4/29/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Post In Case of Fire Do Not Use Elevator signage next to lobby corridor call station. | 4/29/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | 110 volt wiring to 3rd and 4th floor stopping switches in the hoistway needs to be in metal conduit | 4/29/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean elevator car top. | 4/29/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | No maintenance records on site. | 4/29/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | Yes | No | No visual signal during fire recall operation. | 12/16/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.5.5.2 Oil Leakage Collection | No | No | Remove scavenger pump from pit. | 4/29/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Remove standing water/oil mixture from pit | 4/29/2026 |