Inspection
Inspection Details
Equipment ID
22738
22738
Inspection Date
12/14/2022
12/14/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Jeffrey Miller
Jeffrey Miller
Relief Valve Pressure
430
430
Slide
Governor Rope Pull
Door Closing Force
18
18
External ID
17b42a6b-745e-401f-a596-f23815265a28
17b42a6b-745e-401f-a596-f23815265a28
Location
Lincoln Industrial SKF
5148 N Hanley Rd, Berkeley, MO
Phone: (314) 679-4214
5148 N Hanley Rd, Berkeley, MO
Phone: (314) 679-4214
Owner
Attn: Tim Reynolds
Lincoln Industrial SKF
5148 N Hanley Rd, Berkeley, MO 63134
Phone: (314) 679-4214
Email: ryan.relleke@skf.com
Lincoln Industrial SKF
5148 N Hanley Rd, Berkeley, MO 63134
Phone: (314) 679-4214
Email: ryan.relleke@skf.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | 6/17/2020 | |
| conversion | conversion | n/a | No | No | Control space shall have permanent lighting 19 fc. top of hoistway. | 11/3/2020 |
| conversion | conversion | conversion - reinspect | Yes | No | Eye ray remains in operation on Phase I (Reinspect) | 9/5/2018 |
| conversion | conversion | n/a | No | No | 6/17/2020 | |
| conversion | conversion | n/a | No | No | Control space shall have permanent lighting 19 fc. top of hoistway. | 11/3/2020 |
| conversion | conversion | conversion - reinspect | Yes | No | Eye ray remains in operation on Phase I (Reinspect) | 9/5/2018 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.35 - Supply Line and Shutoff Valve | 3.19.4.1 | No | No | A manually operating shutoff valve shall be provided between the hydraulic machines and the hydraulic jack and shall be located outside the hoistway and adjacent to the hydraulic machine. | 6/19/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.32 - Control Valve | 3.19.4.5 | No | No | A pressure gauge fitting with shutoff valve shall be provided on jack side of the check valve or immediately adjacent to the hydraulic control valve. | 6/19/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.32 - Control Valve | 3.19.4.4 | No | No | A manuallly operated valve, located on or adjacent to the control valves, shall be provided and identified, which permits lowering the car at a speed not exceeding 0.10 m/s (20 ft/min). | 6/19/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.37 - Pressure Switch | 3.26.8 Pressure Switch | Yes | No | When cylinders are installed with the top of the cylinder above the top of the storage tank, a pressure switch shall be provided in the line between the cylinder and the valve, which shall be activated by the loss of positive pressure at the top of the cylinder. | 9/24/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 3.4 | Yes | No | When the car rests on its fully compressed buffers or bumpers, there shall be a vertical clearance of not less than 24" between the top of the pit floor and the lowest part, equipment, or device installed beneath the car platform. | 9/24/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | No | No | 2.7.9.1 - Not enough light in hoistway. Control space shall have permanent lighting of 19 foot-candles at top of hoistway. | 11/14/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 9/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | No | No | Light in hoistway shall be 19 foot-candles. (2nd Notice) | 11/14/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency phone shall be operational. (2nd Notice) Elevator will be red-tagged if not corrected within 14 days. | 11/16/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator. | 11/14/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 2.7.5.1 Lighting | No | No | Light in hoistway shall be 19 foot-candles. Note: This violation has been cited multiple years and is still not corrected. Violation will require a re-inspection if not corrected by the next annual inspection. | 11/14/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | The means to restrict the opening of the car door shall be operational. | 2/3/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current operating certificte shall be posted in the elevator equipment room in a noncombustible frak with a clear protective plate over it. | 2/3/2026 |