Inspection
Inspection Details
Equipment ID
16617
16617
Inspection Date
12/28/2022
12/28/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
James VanZant
James VanZant
Mechanic Name
Terry Wingard
Terry Wingard
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
16
16
External ID
399bb99c-6bba-49d6-b038-6d40d0702e01
399bb99c-6bba-49d6-b038-6d40d0702e01
Location
Ferrell-Duncan : The Bone & Joint Center
3555 S National Ave, Springfield, MO
Phone: (417) 875-3988
Email: steve.graham@coxhealth.com
3555 S National Ave, Springfield, MO
Phone: (417) 875-3988
Email: steve.graham@coxhealth.com
Owner
Attn: Steve Graham - Maintenance
Ferrell Duncan Building
1001 E Primrose, Springfield, MO 65807
Phone: (417) 875-3261
Fax: (417) 875-3297
Email: steve.graham@coxhealth.com
Ferrell Duncan Building
1001 E Primrose, Springfield, MO 65807
Phone: (417) 875-3261
Fax: (417) 875-3297
Email: steve.graham@coxhealth.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | isolation pads under machine need replaced | 6/29/2021 | ||
| conversion | conversion | n/a | needs current certificate posted | 6/29/2021 | ||
| conversion | conversion | n/a | Install metal tags for annual & 5 yr safety test to governor | 6/29/2021 | ||
| A17.1-1996 : Elevators | 2.16 -Overhead Beam and Fastenings | 105.3 | isolation pads under machine need replaced | 6/29/2021 | ||
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | x | suspension cables (red rust or rouge) needs attention--lubricate | 9/24/2019 | |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | red dust needs to be vacumed up in machine room NOTE smoke detectors in the machine room | 6/29/2021 | ||
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | current certificate needs to be dis[layed in machine room | 6/29/2021 | ||
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | x | 1001.2(c)(29)(4) ropes rouging /undersize need replaced 120 days to complete | 6/29/2021 | |
| A17.1-1996 : Elevators | 2.16 -Overhead Beam and Fastenings | 105.3 | isolation pads under machine need replaced | 6/30/2021 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | MCP shall be kept in equipment room, including Fire service testing log, recorded monthly. no MCP / Fire test log on-site | 9/25/2024 | ||
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | x | 3.23: Ropes replaced, no rope data tag . | 5/27/2022 | |
| A17.1-1996 : Elevators | 3.23 - Suspension rope | 1001.2(c)(29) | x | 3.23: Ropes replaced, no rope data tag . | 5/27/2022 | |
| A17.1-1996 : Elevators | 3.20 - Governor rope | 1001.2(c)(26) | x | 5.6.2/ 8.11.2.1.5(g) Governor Rope shall be shortened/replaced to allow proper Tension device clearance. REINSPECTION>6/27/22 | 12/28/2022 | |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | REPAIR CARTOP LIGHT WIRING. | 9/25/2024 | ||
| MO Minimum : Elevators | (I) - Pits | (I)1 | REMOVE LARGE BAG OF TRASH FROM PIT.(all units) | 9/25/2024 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | Provide current MCP in machine room | 9/25/2024 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Display current state operating certificate in machine room | 9/25/2024 | ||
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x | provide operational phone in cab | 11/4/2024 | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | provide on site MCP | 12/30/2024 |