Inspection
Inspection Details
Equipment ID
10525
10525
Inspection Date
12/19/2022
12/19/2022
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas Sharp
Thomas Sharp
Mechanic Name
Dustin Arnett
Dustin Arnett
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
385a83a8-c92a-4112-a49f-ea15c6f9eee8
385a83a8-c92a-4112-a49f-ea15c6f9eee8
Location
Badenhaus
8450 GAST PL, SAINT LOUIS, MO
Phone: (314) 286-4267
8450 GAST PL, SAINT LOUIS, MO
Phone: (314) 286-4267
Owner
Attn: Badenhaus
The Habitat Company
8450 Gast Pl, St. Louis, MO 63147
Phone: (314) 286-4267
Email: areeves@habitat.com
The Habitat Company
8450 Gast Pl, St. Louis, MO 63147
Phone: (314) 286-4267
Email: areeves@habitat.com
Billing
Attn: The Habitat Company
The Habitat Company
4451 Forest Park Ave, St. Louis, MO 63108
Phone: (618) 978-3338
Email: ssutherlin@habitat.com
The Habitat Company
4451 Forest Park Ave, St. Louis, MO 63108
Phone: (618) 978-3338
Email: ssutherlin@habitat.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | The cab ceiling is of the open egg-crate type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers. | 7/21/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | The car door restrictor device shall be adjusted so that it will properly catch and restrict opening of the car doors to a maximum of 4 inches when the car is away from the landing zone. Reinspection is required. | 2/11/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to, as used for all inspections. Upon investigation, it was determined that the proper code should be ASME A17.1 1996 . Provide a proper plate on the front of the controller or mainline disconnect. | 7/21/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. | 7/21/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | The cab ceiling is of the open egg-crate type, which does not provide protection from the light bulbs should they shatter. The lights shall be guarded by plastic sleeve or some other means to properly protect passengers. | 7/21/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to, as used for all inspections. Upon investigation, it was determined that the proper code should be ASME A17.1 1996 . Provide a proper plate on the front of the controller or mainline disconnect. | 7/21/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | The elevator machine room cannot be used for storage. Remove the items being stored in the machine room to provide proper room for maintenance to be performed. | 7/21/2020 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Phone in elevator cab does not work. | 1/8/2021 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Fire service is not working on Phase II. Re-inspection required | 6/12/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/28/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | No | No | The car-top emergency exit shall be secured to prevent it from falling down the hoistway. | 1/28/2025 |
| A17.1-1996 : Elevators | 2.4 - Machine space | 101.2 | No | No | Equipment in the machine room not being used in conjunction with the function or use of the elevator shall be removed. | 1/28/2025 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car telephone shall be operational. Note: The phone dials out but isn't answered and outputs an audible alert of "service suspended". | 9/3/2024 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 211.2 | Yes | No | The emergency/standby power shall be tested. | 9/3/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No State operating certificate in the machine room. | 11/21/2025 |