Inspection
Inspection Details
Equipment ID
13141
13141
Inspection Date
1/3/2023
1/3/2023
Inspection Type
Special Inspection
Special Inspection
Inspector Name
Melvin Barks Jr.
Melvin Barks Jr.
Mechanic Name
Relief Valve Pressure
N/A
N/A
Slide
Governor Rope Pull
Door Closing Force
External ID
79db9f1c-fb7c-4913-82b8-dc1395ab5946
79db9f1c-fb7c-4913-82b8-dc1395ab5946
Location
Comfort Inn- Pacific
1320 Thornton St, Pacific, MO
Phone: (636) 257-4600
1320 Thornton St, Pacific, MO
Phone: (636) 257-4600
Owner
Attn: Comfort Inn-Pacific
Comfort Inn-Pacific
1320 Thornton St, Pacific, MO 63069
Phone: (000) 000-0000
Comfort Inn-Pacific
1320 Thornton St, Pacific, MO 63069
Phone: (000) 000-0000
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | Perform OSV test. Tag and seal upon completion. | 1/5/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Fire extinguisher in machine room is expired. Replace or have serviced | 1/9/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone in car does not work, appears to be an issue with the line. Re-inspection required | 1/9/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 1/9/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | OSV is overdue for testing as noted in last inspection. Perform required testing, seal & tag within 90 days. Re-inspection required | 1/9/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Remove all non elevator related wiring from machine room, including coaxial cable & power for tv in adjacent room | 1/9/2023 |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.1 | No | No | Wiring for exhaust fan in machine room shall be made permanent, be grounded & be properly enclosed in conduit per NFPA 70 | 1/9/2023 |
| A17.1-1996 : Elevators | 2.8 - Pipes, wiring, and ducts | 102.1 | No | No | Remove unused wiring connected to exhaust fan switch in machine room or use power fan in accordance with NFPA 70 | 1/9/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Phone failed to operate | 1/9/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of current state operating certificate shall be properly displayed in machine room | 12/2/2025 |
| A17.1-1996 : Elevators | 1.17 - Standby power operation | 1002.2g (Standby Power Operation) | Yes | No | Emergency recovery lowering device is inoperable. repair and reinspect 3.26.10 | 12/2/2025 |