Inspection
Inspection Details
Equipment ID
19775
19775
Inspection Date
12/19/2022
12/19/2022
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Craig Kinmann
Craig Kinmann
Relief Valve Pressure
560
560
Slide
Governor Rope Pull
Door Closing Force
17F/19R
17F/19R
External ID
f2487fa6-7fb5-4723-932d-81e21c2b799d
f2487fa6-7fb5-4723-932d-81e21c2b799d
Location
First Bank-Webster Groves
11 E LOCKWOOD AVE, WEBSTER GROVES, MO
Phone: (314) 301-4500
11 E LOCKWOOD AVE, WEBSTER GROVES, MO
Phone: (314) 301-4500
Owner
Attn: Brian Choplin
First Bank Property Mgmt
7495 Watson Rd, St. Louis, MO 63119
Phone: (314) 587-4705
Email: Brian.choplin@fbol.com
First Bank Property Mgmt
7495 Watson Rd, St. Louis, MO 63119
Phone: (314) 587-4705
Email: Brian.choplin@fbol.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5.1 Examination and Maintenance of Packing Glands and Seals | Yes | No | The hydraulic cylinder packing is leaking excessively and corrective action shall be taken. | 12/14/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | The fire extinguisher in the machine room is expired and shall be serviced or replaced with another code compliant fire extinguisher. | 12/16/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) | 1/6/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 1/6/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 1/6/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 1/6/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Fire service testing shall be documented monthly. | 1/6/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)2 | No | No | Repair car buffer, set-bolt is stripped. | 1/6/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone will not dial out. Take corrective action and re-test. | 1/31/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 1/16/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)2 | No | No | Repair car buffer, set-bolt is stripped. | 1/16/2026 |