Inspection
Inspection Details
Equipment ID
18621
18621
Inspection Date
12/21/2022
12/21/2022
Inspection Type
Reinspection
Reinspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
Travis Gast
Travis Gast
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
fb8d60b4-8ef4-4dfe-bdd3-6a4a705f1323
fb8d60b4-8ef4-4dfe-bdd3-6a4a705f1323
Location
Time Stone Building
1314 Washington Ave, St. Louis, MO
Phone: (310) 920-4433
1314 Washington Ave, St. Louis, MO
Phone: (310) 920-4433
Owner
Attn: Time Stone LLC c/o MBD Management LLC
Time Stone LLC c/o MBD Management LLC
1220 St. Charles St, St. Louis, MO 63103
Phone: (310) 920-4433
Email: ranchoffice@protonmail.com
Time Stone LLC c/o MBD Management LLC
1220 St. Charles St, St. Louis, MO 63103
Phone: (310) 920-4433
Email: ranchoffice@protonmail.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 1/27/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | No | No | Provide code compliant machine room lighting. | 2/14/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.11.2.1.5(b) | Yes | No | Provide code compliant bottom runby clearance. | 1/27/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.22 - Wire rope fastening and hitch plate | 8.6.3 | Yes | No | 8.6.3.3.2(a) - Shackle nuts on the bottom of the counterweight and are loose. | 5/3/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.1 | No | No | There is a 2 x 4 inch electrical box on the wall of the machine room with exposed wires, cover the box. | 2/14/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 2/14/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 8.11.2.1.2(k) | No | No | The disconnect located in the machine space shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 2/14/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Rope tag for the governor rope are missing. | 2/14/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.27 - Rope fastenings | 8.11.2.1.2(y) | No | No | Wedge rope socket is anchored incorrectly. When the steel wire rope has been seated in the wedge socket by the load on the rope, the wedge shall be visible, and at least two wire-rope retaining clips shall be provided to attach the termination side to the load-carrying side of the rope. The first clip shall be placed a maximum of 4 times the rope diameter above the socket, and the second clip shall be located within 8 times the rope diameter above the first clip. | 2/14/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Fire service testing log & evacuation procedures are missing as well. | 2/14/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.6 Stop Switches in Pit (Re-Inspection) | Yes | No | The second stop switch in the pit is defective, replace. | 5/3/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2.1 Phase 1 Emergency Recall OperationBy Fire Alarm initiating Devices | Yes | Yes | Install a fire alarm initiating device at the basement level and the top of the hoistway. | 5/3/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | The following testing items still need to be witnessed to complete the annual inspection and category 5 test: 1. Fire service., 2. Compress car buffer with rated load., 3. Compress counterweight buffer with empty car., 4. Brake test stop and hold 125% rated load., 5. Brake test will hold 125% load with main power removed., 6. Unintended motion device will stop and hold 125 % rated load in down direction., 7. Unintended motion will stop and hold empty car in the up direction., 8. Pull out/pull thru., 9. Governor switch/jaw., 10. Set car safeties., 11. Phone, light, and bell with 110v power removed. | 5/3/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 2.24.8.3 | Yes | Yes | The driving-machine brake, on its own, shall be capable of stopping & holding 125% of the rated load. Elevator Red Tagged. | 9/1/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2.1 Phase 1 Emergency Recall OperationBy Fire Alarm initiating Devices | Yes | Yes | A fire alarm initiating device shall be installed at the top of the hoistway. | 9/1/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | The following testing items still need to be witnessed to complete the annual inspection and category 5 test: 1. Fire service., 2. Compress car buffer with rated load., 3. Compress counterweight buffer with empty car., 4. Brake test stop and hold 125% rated load., 5. Brake test will hold 125% load with main power removed., 6. Unintended motion device will stop and hold 125 % rated load in down direction., 7. Unintended motion will stop and hold empty car in the up direction., 8. Set car safeties., 9. Phone, light, and bell with 110v power removed. | 9/1/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.42 Seismic (Earthquake protection) | 8.4.10 | Yes | No | The counterweight derailment device shall be operational. | 10/18/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate. | 2/14/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Provide monthly firemans' return test results. | 2/14/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency phone shall be operational. | 10/18/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.17 - Drive machine brake | 8.6.4.19.11 A17.1 2016 Ascending Overspeed Protection, Unintended Movement Devices, and Emg Brake | Yes | Yes | The unintended motion device (rope gripper) shall stop the car in 48" or less when activated. Elevator Red Tagged. | 10/18/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11 Periodic Inspection and Test. | Yes | No | The following items have yet to be tested: 1. Set safeties., 2. Compress car buffer with rated load., 3. Compress counterweight buffer with empty car., 4. Check door pressure., 5. Unintended motion in up direction. | 10/18/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) | 8.4.10 Emegency Operation and Signaling Devices | Yes | No | The counterweight derailment device shall be operational. | 12/21/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state operating certificate. | 2/14/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | Provide monthly firemans' return test results. | 2/14/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency phone shall be operational. | 12/21/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | No | No | Maintenance Control Program (MCP) shall be available in machine room | 8/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.19 - Car Ride | 2.15.2 | No | No | Roller guide on car top needs replaced | 8/28/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.14 - Code data plate | 8.9 | No | No | Controller shall have a code data plate stating "A17.1-2000" | 8/28/2025 |