Inspection
Inspection Details
Equipment ID
7177
7177
Inspection Date
1/6/2023
1/6/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Mitchell McNeely
Mitchell McNeely
Mechanic Name
Jake Brennan
Jake Brennan
Relief Valve Pressure
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
23
23
External ID
aa48d590-d4c3-456f-b152-b27d6d0edcc4
aa48d590-d4c3-456f-b152-b27d6d0edcc4
Location
Justus Holdings, LLC
1405 Pine St, St. Louis, MO
Phone: (314) 698-3060
1405 Pine St, St. Louis, MO
Phone: (314) 698-3060
Owner
Attn: Justus Holdings, LLC
Spirit On Pine LP
721 W Hwy 50, O'Fallon, IL 62269
Phone: (314) 361-7067
Email: raj@tutandtut.com
Spirit On Pine LP
721 W Hwy 50, O'Fallon, IL 62269
Phone: (314) 361-7067
Email: raj@tutandtut.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established. Repair/replace this phone for proper operation and passenger safety. Reinspection required. | 5/21/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. | 5/21/2026 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1f (Stop Switch in Pits) | No | No | The elevator pit exceeds 66” and is required a second stop switch in the pit that conforms to A17.1 1995 edition. | 5/21/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher in the machine room shall be serviced, the last annual service tag indicates it was serviced in 2023 | 5/21/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | The elevator car top shall be cleaned of spare parts. | 5/21/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. | 5/21/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate | No | No | There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to, as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. | 5/21/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The car traveling cable, underneath the car, has rubbed through the outer insulation in a couple of locations as the car reaches the lobby. Confirm that no internal wires have been affected and repair or replace traveling cable. | 5/21/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | At the top of the hoistway all conduit junction boxes are required to have the proper covers installed. | 5/21/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established. Repair/replace this phone for proper operation and passenger safety. Reinspection required. | 5/26/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | Yes | No | The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. | 5/26/2026 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1f (Stop Switch in Pits) | Yes | No | The elevator pit exceeds 66” and is required a second stop switch in the pit that conforms to A17.1 1995 edition. | 5/26/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Yes | No | The fire extinguisher in the machine room shall be serviced, the last annual service tag indicates it was serviced in 2023 | 5/26/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | Yes | No | The elevator car top shall be cleaned of spare parts. | 5/26/2026 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. | 5/26/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate | Yes | No | There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to, as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. | 5/26/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | Yes | No | The car traveling cable, underneath the car, has rubbed through the outer insulation in a couple of locations as the car reaches the lobby. Confirm that no internal wires have been affected and repair or replace traveling cable. | 5/26/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | Yes | No | At the top of the hoistway all conduit junction boxes are required to have the proper covers installed. | 5/26/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Cat 5 testing still needs to be performed. Re-inspection required | 5/26/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established. Repair/replace this phone for proper operation and passenger safety. Reinspection required. | |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | Yes | No | This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. |