Inspection
Inspection Details
Equipment ID
2082
2082
Inspection Date
1/11/2023
1/11/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Wright
Michael Wright
Mechanic Name
Michael Bales
Michael Bales
Relief Valve Pressure
580
580
Slide
Governor Rope Pull
Door Closing Force
24/22
24/22
External ID
2c6f4a43-b161-4f3e-8947-7db686b66d17
2c6f4a43-b161-4f3e-8947-7db686b66d17
Location
Rediscover Administration
1547 NE Rice Rd, Lee's Summit, MO
Phone: (816) 347-3253
1547 NE Rice Rd, Lee's Summit, MO
Phone: (816) 347-3253
Owner
Attn: Rediscover Administration
Rediscover Administration
1555 NE Rice Rd, Lee's Summit, MO 64086
Phone: (816) 347-3275
Email: medwards@rediscovermh.org
Rediscover Administration
1555 NE Rice Rd, Lee's Summit, MO 64086
Phone: (816) 347-3275
Email: medwards@rediscovermh.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | pit has water an oil standing in it | 5/21/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | emg. phone not working | 1/11/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | oil on pit floor | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt of operation displayed | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Repair the emergency phone. | 1/19/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean the pit floor, standing oil. | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Mach room door is defeatable | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | mach room has non elev. related materials stored in it | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | pit floor has oil covering it clean same | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | emg phone not working | 1/9/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt. displayed | |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | mach room door is defeatable needs to be made undefeatable | |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | oil covering pit floor | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current cirt displayed |