Inspection
Inspection Details
Equipment ID
1981
1981
Inspection Date
1/10/2023
1/10/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Raymond Stidham
Raymond Stidham
Mechanic Name
Stephen Long
Stephen Long
Relief Valve Pressure
440
440
Slide
Governor Rope Pull
Door Closing Force
26
26
External ID
8bead0be-ecee-4720-b1a2-ca86bc79fb29
8bead0be-ecee-4720-b1a2-ca86bc79fb29
Location
3M Company
2120 E Austin Blvd, Nevada, MO
Phone: (417) 667-7851
2120 E Austin Blvd, Nevada, MO
Phone: (417) 667-7851
Owner
Attn: Don Rodulfo
3M Company
PO Box 33121, St. Paul, MN 55133
Phone: (417) 283-0366
Alt Phone: (816) 729-8533
Email: dtrodulfo@mmm.com
3M Company
PO Box 33121, St. Paul, MN 55133
Phone: (417) 283-0366
Alt Phone: (816) 729-8533
Email: dtrodulfo@mmm.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-1996 : Elevators | 1.1 - Door Re-opening device | 1001.2(a)(1) | No | No | Both front and rear gate reopening devises need replaced | 2/7/2020 |
| A17.1-1996 : Elevators | 1.5 - Car lighting and receptacles | 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) | Yes | No | Must make Emergency light operable. 1.5 | 1/9/2023 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1004.2(a)(6) (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must make Emergency alarm operable. 1.6 | 1/9/2023 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | No | No | Elevator pit must be kept free of Debris. 8.6.4.7 | 1/24/2023 |
| A17.1-1996 : Elevators | 1.1 - Door Re-opening device | 1001.2(a)(1) | No | No | Rear Gate Re-opening devise must be made operable. 1001.2(a)(1) | 1/24/2023 |
| A17.1-1996 : Elevators | 1.1 - Door Re-opening device | 1001.2(a)(1) | No | No | Must repair or replace Protective Boot for gate re-opening device front gate. 1001.2(a)(1). (cuts tears and missing section) | 1/24/2023 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.7 Firefighter' Service Operating Procedures | No | No | Must make Phase II fire service operable. 211.7 ( doors operate properly but car will not leave primary floor) | 1/24/2023 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must Make Emergency Alarm Operable. 8.6.4.15 | 4/22/2026 |
| A17.1-1996 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 211.8 Switch Keys | No | No | Must make Phase II Fire Service Key Switch Operable. 6.4 | 4/22/2026 |
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | Must perform Cat 5 OSV (over speed valve)test/insp. | 4/22/2026 |
| A17.1-2016 : Elevators | 1.1 - Door Reopening Device | 8.11.2.1.1(a) | No | No | Must make Car Gate Reopening devise operable. 1.18 | |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Must make emergency alarm bell operable. 1.6 |