Inspection
Inspection Details
Equipment ID
16499
16499
Inspection Date
1/19/2023
1/19/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Andrew Schmitz
Andrew Schmitz
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
c3ad1acc-4055-4ca1-a8ae-6d797f76bcf4
c3ad1acc-4055-4ca1-a8ae-6d797f76bcf4
Location
Hampden Hall Apts
4400 McPherson Ave, St. Louis, MO
Phone: (314) 652-4400
4400 McPherson Ave, St. Louis, MO
Phone: (314) 652-4400
Owner
Attn: Revival STL Construction, LLC
Revival STL Construction, LLC
PO Box 46721, St. Louis, MO 63146
Phone: (314) 852-6755
Email: anshul@revivalstl.com
Revival STL Construction, LLC
PO Box 46721, St. Louis, MO 63146
Phone: (314) 852-6755
Email: anshul@revivalstl.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Cab light diffusers (ceiling) are missing and shall be replaced. | 4/19/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Cab emergency telephone does not work and shall be repaired and tested. | 2/19/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Elevator will not pick up its rated capacity (2500 lbs). The elevator hoist machine shall be repaired and tested. | 2/20/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Replace the missing door gib on the 6th & 8th floor. | 4/19/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Replace the missing hoistway door gib on the 6th & 8th floor. | 4/19/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | The car door restrictor shall be operational. | 5/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The phase 1 & phase 2 fire service key switches shall be legible. | 9/30/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency telephone shall be operational. | 5/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The emergency lights shall be operational. | 5/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The alarm bell shall be operational. | 5/1/2020 |
| MO Minimum : Elevators | (A) - Hoistways | (A)3 | No | No | The missing pickup roller on the 13th floor hall door shall be replaced. | 9/30/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Remove the debris from the pit. The pit shall be kept clean. | 9/30/2019 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | The exposed wiring in the pit which is not part of the elevator shall be removed. | 9/30/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | The car door restrictor shall be operational. | 8/13/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The emergency lights shall be operational. | 8/13/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The alarm bell shall be operational. | 8/13/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Replace missing hoistway door gib on 4th floor | 12/30/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Adjust hoist rope shackle so that is does not contact sheet metal on top of counterweight, causing uneven rope tension | 12/30/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Reprogram emergency phone to provide 2 way communication | 1/21/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Repair inoperative Emergency Phone | 1/19/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Repair inoperative emergency light | 1/19/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Repair exposed door motor wiring | 1/19/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Replace missing door gib on 2nd floor door | 1/19/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Provide current year tested fire extinguisher in the elevator machine room. | 10/1/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Machine room ventilation fan is not working. Repair/replace as needed. | 10/1/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)1 | No | No | Car directional lens is missing, replace. | 10/1/2023 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Fire extinguisher shall be kept up to date. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Car Top needs cleaned | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Machine room need cleaned | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Pit needs cleaned | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Greenfield on Car top need secured | |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Hoist ropes are undersized and need replaced (90 day reinspect) | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | In car push/pull stop switch shall activate alarm bell | |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency Light and alarm is not working | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit Light not working |