Inspection
Inspection Details
Equipment ID
2036
2036
Inspection Date
1/17/2023
1/17/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
Jasen Kennedy
Jasen Kennedy
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
26
26
External ID
6aae3325-cb93-4518-a92f-b0064f81b99b
6aae3325-cb93-4518-a92f-b0064f81b99b
Location
Pleasant Lea Junior High School
630 SW Persels Rd, Lee's Summit, MO
Phone: (816) 986-1175
630 SW Persels Rd, Lee's Summit, MO
Phone: (816) 986-1175
Owner
Attn: Lee's Summit R-7 School District
Lee's Summit R-7 School District
502 Transport Dr, Lee's Summit, MO 64081
Phone: (816) 986-2181
Email: matthew.tillman@lsr7.net
Lee's Summit R-7 School District
502 Transport Dr, Lee's Summit, MO 64081
Phone: (816) 986-2181
Email: matthew.tillman@lsr7.net
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light switch is an old pit stop switch. Change to conventional light switch, very confusing. | 3/27/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working properly, alarm bell ok. | 7/19/2019 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working. | 1/21/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | Door rollers bad on car slow door. | 1/21/2021 |
| MO Minimum : Elevators | (G)2-Alterations | 8.7.2.14.2 Car Enclosure | Yes | No | Emergency phone not working. | 1/21/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | No | No | Emergency phone not working. | 1/18/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.11.1 Firefighters' Emergency Operation & Documentation | No | No | Fire service testing log not up to date. | 3/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | Car and landing door rollers badly worn, causing vibration. | 1/17/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working, alarm bell ok. | 2/17/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working, alarm bell ok. | 3/27/2026 |
| MO Minimum : Elevators | (S) - Fire Service | 211.8 Switch Keys | No | No | Phase I recall switch vandalized, repair. | 3/27/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working, alarm bell ok. |