Inspection
Inspection Details
Equipment ID
2881
2881
Inspection Date
9/26/2018
9/26/2018
Inspection Type
Reinspection
Reinspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
Relief Valve Pressure
Slide
Na
Na
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
External ID
9bcdca98-d7e1-40a0-a12d-70edec7c3353
9bcdca98-d7e1-40a0-a12d-70edec7c3353
Location
Upton Pump Station
7400 REILLY AVE, ST. LOUIS, MO
7400 REILLY AVE, ST. LOUIS, MO
Owner
Metropolitan Sewer District STL
2350 MARKET ST, SAINT LOUIS, MO 63103-2519
2350 MARKET ST, SAINT LOUIS, MO 63103-2519
Billing
Attn: Metropolitan Sewer District
2350 MARKET ST, SAINT LOUIS, MO 63103-2519
2350 MARKET ST, SAINT LOUIS, MO 63103-2519
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Install guard on floriscent lights in car | 9/26/2019 |
| conversion | conversion | n/a | No | No | Post current state certificate in machine room space | 9/26/2019 |
| conversion | conversion | n/a | No | No | Repair alarm bell in car | 9/26/2019 |
| Missouri Minimum : Manlifts | (V) - Existing Manlifts | (V)1 | No | Yes | Put red tag on lift. No active phone line. | 4/28/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The original access door on the controller was removed or misplaced and replaced with a combustible door .Controller Access panel must be made of a non combustible material | 8/6/2020 |
| MO Minimum : Elevators | (R) - Power Operated Special Purpose Elevators | (R)6 | No | Yes | The current hoistway door interlock does not prevent the door from being opened when the car is away from the landing. The door shall be provided with approved interlocks | 8/6/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The Current operating certificate shall be posted in the machine room in a non combustible frame | 8/6/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | There shall be maintenance records in the elevator machine room or accessible to the inspector. Shall consist of maintenance task such as callbacks, examinations, test, adjustments, and replacements. | 8/6/2020 |
| MO Minimum : Elevators | (M) - Car Safeties and Speed Governors | (M)1 | Yes | Yes | The car safeties shall be capable of stopping the rated load of the car. | 9/15/2020 |
| MO Minimum : Elevators | (R) - Power Operated Special Purpose Elevators | (R)9 | Yes | Yes | Doors shall be equipped with an interlocks. | 10/9/2020 |
| MO Minimum : Elevators | (D) - Brakes | (D)2 | Yes | Yes | Brake shall stop and hold car with 125% rated load. Unit red tagged until repaired. | 10/9/2020 |
| MO Minimum : Elevators | (R) - Power Operated Special Purpose Elevators | (R)9 | Yes | Yes | Doors shall be equipped with an interlock. Red tagged unit. |