Inspection
Inspection Details
Equipment ID
9747
9747
Inspection Date
1/16/2023
1/16/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Benjamin Williams
Benjamin Williams
Relief Valve Pressure
550
550
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
66388ff3-e90f-4e20-8fb2-dcd03400f92e
66388ff3-e90f-4e20-8fb2-dcd03400f92e
Location
Central Park Apartments
5386 PERSHING AVE # 90, SAINT LOUIS, MO
Phone: (314) 327-2035
5386 PERSHING AVE # 90, SAINT LOUIS, MO
Phone: (314) 327-2035
Owner
Attn: Revival STL Construction, LLC
Revival STL Construction, LLC
PO Box 46721, St. Louis, MO 63146
Phone: (314) 852-6755
Email: anshul@revivalstl.com
Revival STL Construction, LLC
PO Box 46721, St. Louis, MO 63146
Phone: (314) 852-6755
Email: anshul@revivalstl.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Machine room door needs to be self closing and locking. | 4/9/2019 |
| conversion | conversion | conversion - reinspect | Yes | No | Car emergency telephone does not work. Needs to be programmed to a 24 hour source. | 11/2/2018 |
| conversion | conversion | n/a | No | No | The elevator in the down direction will not stop at the designated floors. Goes straight to the bottom floor. | 4/9/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The fire extinguisher in the machine room is expired. | 4/9/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)3 | No | No | Ceiling in machine room is damaged. | 4/9/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)3 | No | No | Water is entering machine room from damaged ceiling next to mainline disconnect creating a life and limb hazard. - Re-Inspection Required | 4/9/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Machine room door shall be self-closing. | 4/9/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | The car top shall be cleaned. | 4/9/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be cleaned. | 4/9/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The machine room fire extinguisher is expired and shall be re-certified or replaced. | 8/21/2019 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall be self-locking and self-closing. | 8/21/2019 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. | 8/21/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | No fire extinguisher in machine room. | 12/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Cartop shall be kept clean. | 12/1/2020 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display updated state operating certificate in machine room. | 12/1/2020 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be kept clean. | 12/1/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone shall work. | 12/18/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide MCP. | 3/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | None. | 3/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean car top. | 3/1/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit. | 3/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Door restrictor broken. | 3/21/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Replace missing selector cover on car top. | 3/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Replace missing dust cover hoist way door, top floor. | 3/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.8 Cleaning of Machine Rooms and Machinery Spaces | No | No | Observed black mold on ceiling,abate as needed. | 3/1/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Resubmit - Clean elevator pit | 3/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Resubmit - Replace missing selector cover on car top | 3/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Resubmit Replace missing dust cover on top floor hoistway door | 3/1/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | Yes | No | Fire extinguisher in machine room is expired, replace or have serviced. Re-inspection required | 5/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | Yes | No | Cartop still needs to be cleaned. Re-inspection required | 5/8/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Yes | No | A copy of the current state operating certificate shall be on display in the machine room. Re-inspection required | 5/8/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | Yes | No | Pit still needs to be cleaned. Re-inspection required | 5/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | A written copy of the MCP shall be kept in the machine room for each unit. Re-inspection required | 3/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | Yes | No | Re-install cover on cartop selector electrical box. Re-inspection required | 5/8/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Hoistway dust covers still need to be re-installed and/or replaced as needed. Re-inspection required | 3/12/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Remove unused traveling cable from car and hoistway | 3/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | Car top selector box shall be covered | 3/12/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Car top shall be cleaned | 3/12/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Pit shall be cleaned. | 3/12/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current operating certificate shall be displayed in machine room | 3/12/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Machine room shall be cleaned | 3/12/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Roof in machine room is leaking water near mainline disconnect. Roof and leak shall be repaired. | 3/12/2026 |
| A17.1-2016 : Elevators | 1.12 - Car enclosure | 2.14.1.9 | Yes | No | Car Sill is warped and presents a trip hazard, shall be replaced | 4/17/2026 |