Inspection
Inspection Details
Equipment ID
10050
10050
Inspection Date
9/20/2018
9/20/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Clyde Johnson
Clyde Johnson
Mechanic Name
Douglas Gildehaus
Douglas Gildehaus
Relief Valve Pressure
390
390
Slide
Governor Rope Pull
Door Closing Force
19
19
External ID
b87b4e73-1423-4687-ac99-3ac29df91f9f
b87b4e73-1423-4687-ac99-3ac29df91f9f
Location
Ballas Medical Office Center
777 S NEW BALLAS RD, CREVE COEUR, MO
777 S NEW BALLAS RD, CREVE COEUR, MO
Owner
Scott Properties
1065 EXECUTIVE PARKWAY DR STE 300, CREVE COEUR, MO 63141-6368
1065 EXECUTIVE PARKWAY DR STE 300, CREVE COEUR, MO 63141-6368
Billing
Attn: Tina Moser, Property Manager
1065 EXECUTIVE PARKWAY DR STE 300, SAINT LOUIS, MO 63141-6368
1065 EXECUTIVE PARKWAY DR STE 300, SAINT LOUIS, MO 63141-6368
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Replace roustabout fitting on supple line near pump unit | 11/7/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Cut off Channel on car top blocking escape hatch. 165" clear opening required. | 9/20/2018 |
| conversion | conversion | n/a | No | No | Replace bad battery in hatch latch for proper operation. | 11/7/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Fire extinguisher needs to be serviced. 2.7.1 | 11/7/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Fasia in hoistway between 2nd and 3rd floor is loose/missing screws. | 10/20/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)12 (Door open zones) | Yes | No | Car door restrictor battery back-up does not work. | 4/17/2020 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)3 | No | No | Cut off car top channel blocking emergency exit. | 10/20/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Replace hatch latch back up battery. | 10/20/2020 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)9 | No | No | Disconnecting means are hard to get to causing a safety hazard. Mechanic has to touch to shut diconnect | |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Pit light does not work | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | OSV is not sealed and must have a category 5 weight test within 90 days or less | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | Perform the required Cat 5 Tests on the overspeed valve | 10/12/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to perform the required Cat 5 testing on the plunger gripper. Re-inspection required |