Inspection
Inspection Details
Equipment ID
1679
1679
Inspection Date
1/26/2023
1/26/2023
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
Slide
10.5”
10.5”
Governor Rope Pull
150/395
150/395
Door Closing Force
16
16
External ID
c51328c0-6757-460e-aba9-63c6703a6710
c51328c0-6757-460e-aba9-63c6703a6710
Location
Wainwright State Office Bldg
111 N 7th St, Rm 111, St. Louis, MO
Phone: (314) 340-6801
111 N 7th St, Rm 111, St. Louis, MO
Phone: (314) 340-6801
Owner
Attn: INTERAGENCY
Wainwright Building-AFMDC
111 N 7th St, Rm 111, St. Louis, MO 63101
Phone: (000) 000-0000
Email: Linda.Sorenson@oa.mo.gov
Wainwright Building-AFMDC
111 N 7th St, Rm 111, St. Louis, MO 63101
Phone: (000) 000-0000
Email: Linda.Sorenson@oa.mo.gov
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.4.2 | Yes | No | A17.1 - 2.4.2.1 BTTM CLEARANCE, RUNBY & MINIMUM REFUGE SPACE, COUNTERWEIGHT RUNBY 4 1/2", NEED TO SHORTEN ROPES. MINIMUM 8.25", RE-INSPECTION REQUIRED | 12/29/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | Yes | No | Provide testing of Phase I operations. | 11/9/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | Yes | No | Provide testing of Phase II operation. | 11/9/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide testing of elevator on emergency power. | 11/9/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | Yes | No | Provide testing of emergency power selector switch. | 11/9/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Worm shaft seal is worn and leaking, repair as needed. | 11/9/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state elevator certificate. | 11/9/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current State Elevator Certificate. | 11/9/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.3.3.3 Runby & Clearances After Reroping or shortening | Yes | No | Provide code compliant hoist rope run by. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Provide testing of the elevator on emergency power. | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.12 - Standby power selection switch | 2.27.2 | Yes | No | Provide testing of the elevator emergency power selector switch. |