Inspection
Inspection Details
Equipment ID
11898
11898
Inspection Date
1/9/2023
1/9/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
Sean Carmody
Sean Carmody
Mechanic Name
James DeBell
James DeBell
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
eeea95a2-5c9f-4d7d-9090-0f1bcbb97447
eeea95a2-5c9f-4d7d-9090-0f1bcbb97447
Location
The Dial Corporation
6901 McKissock Ave, St. Louis, MO
Phone: (636) 232-1045
Email: Robert.Brown@henkel.com
6901 McKissock Ave, St. Louis, MO
Phone: (636) 232-1045
Email: Robert.Brown@henkel.com
Owner
Attn: Henkel
Henkel
6901 McKissock Ave, St. Louis, MO 63147
Phone: (636) 544-1911
Email: Lawrence.Pellicano@henkel.com
Henkel
6901 McKissock Ave, St. Louis, MO 63147
Phone: (636) 544-1911
Email: Lawrence.Pellicano@henkel.com
Billing
Attn: Henkel
Henkel
6901 McKissock Ave, St. Louis, MO 63147
Phone: (636) 544-1911
Email: Kaci.Figueroa@henkel.com
Henkel
6901 McKissock Ave, St. Louis, MO 63147
Phone: (636) 544-1911
Email: Kaci.Figueroa@henkel.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Need a maintenance control program on site posted on controller in machine room | 9/29/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | On phase II fire service, hold feature not working | 9/29/2020 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service and document on log in machine room | 10/1/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Service Fire extinguisher on west wall of the machine room | 10/1/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | Each elevator shall be provided with lighting and a duplex receptable fixture on the car top. The lighting shall be permanently connected, fixed, or portable, or a combination thereof, to provide an illumination level of not less than 100 lx measured at the point of any elevator part or equipment, where maintenance or inspection is to be performed from the car top. | 10/6/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 1/9/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The category 5 test and the annual inspection are incomplete. Fire service, full load safety test, pull out/pull thru, SOS, inspect the pit, and runby still all need to be checked/tested. | 1/9/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | Yes | Unit red tagged because the governor rope would not pull thru after reaching a force of 1200 lbs. | 4/10/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The category 5 test and the annual inspection are incomplete. Fire service, full load safety test, pull out/pull thru, SOS, inspect the pit, and runby still all need to be checked/tested. | 4/10/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 4/10/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lighting needs to be repaired. One or more fixtures are not working properly. | 10/6/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Audible device for timed/automatic freight door closing does not work properly. | 9/5/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Replace missing hall fire signage "in case of fire..". | 10/6/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lighting needs to be repaired unlit bulbs | 10/6/2025 |