Inspection
Inspection Details
Equipment ID
14723
14723
Inspection Date
1/16/2023
1/16/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Michael Ledden
Michael Ledden
Mechanic Name
Phillip Moise, Jr.
Phillip Moise, Jr.
Relief Valve Pressure
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
f37e9476-17d1-4263-85d4-d4c77fff3c74
f37e9476-17d1-4263-85d4-d4c77fff3c74
Location
Union Ave Christian Church
733 Union Blvd, St. Louis, MO
Phone: (314) 361-8844
733 Union Blvd, St. Louis, MO
Phone: (314) 361-8844
Owner
Attn: Ron Lindsey
Union Ave Christian Church
733 Union Blvd, St. Louis, MO 63108
Phone: (000) 000-0000
Email: rlindsey@union-avenue.org
Union Ave Christian Church
733 Union Blvd, St. Louis, MO 63108
Phone: (000) 000-0000
Email: rlindsey@union-avenue.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 1/9/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. | 1/9/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 1/9/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | The 1st floor hall and car call buttons shall be operational. | 1/9/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | All means of access to elevator machine rooms shall be of a permanent nature and shall be constructed and maintained in a clear and unobstructed manner. Access to the roof shall not be fold out ladder. | 1/9/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | MCP required on site | 11/10/2023 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Ensure that ladder to access roof/machine room is safe. | 11/10/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (1) Minimum Standard | Yes | Yes | Ropes slip traction during 125% weight testing. Unit has been red-tagged. | 11/3/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | The pit light shall work. | 11/10/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. Remove excess debris. | 11/10/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 11/10/2023 |