Inspection
Inspection Details
Equipment ID
10762
10762
Inspection Date
2/6/2023
2/6/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Walter Tauchert
Walter Tauchert
Relief Valve Pressure
520
520
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
66bffd6b-3ac0-4fd8-9941-c66d6e666b20
66bffd6b-3ac0-4fd8-9941-c66d6e666b20
Location
Winghaven MOB
5551 Winghaven Blvd, O'Fallon, MO
Phone: (314) 972-2360
5551 Winghaven Blvd, O'Fallon, MO
Phone: (314) 972-2360
Owner
Attn: HTA-Medical Portfolio 2, LLC #141105
Healthcare Trust of America c/o AvidXchange
PO Box 32771, Charlotte, NC 28232
Phone: (636) 288-8589
Email: DavidConwell@htareit.com
Healthcare Trust of America c/o AvidXchange
PO Box 32771, Charlotte, NC 28232
Phone: (636) 288-8589
Email: DavidConwell@htareit.com
Billing
Same as Owner
Violations
Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-1996 : Elevators | 2.41 - Maintenance Records | 8.6.1.4 | Provide on site written maintenance control program. | 1/28/2025 | ||
A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | OSV is not sealed. Perform test on or before next annual inspection. | 1/28/2025 | ||
A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) | x | Unsealed. See 4/23/21 report. | 2/6/2023 | |
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Expired | 1/28/2025 | ||
A17.1-1996 : Elevators | 2.32 - Control Valve | 303 | Car failed 15 minute stand test. Tech determined leaking back through valve. Repair/replace as needed. Reinspect. | 1/28/2025 | ||
A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1 | Sump hole filled with oil, remove. Determine if sump pump works, if not replace. | 1/28/2025 | ||
A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 1001.2(a)(15) | Floor’LL’ (r) braille/tactile plate missing, replace. | 1/28/2025 | ||
A17.1-1996 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | x | See ‘21 report for OSV. THIRD NOTICE | 11/13/2024 | |
A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | Post current State Elevator Certificate. | 1/28/2025 | ||
A17.1-1996 : Elevators | 2.32 - Control Valve | 303 | Car failed 15 minute stand test, repair as needed. SECOND NOTICE. | 1/28/2025 | ||
MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | x | OSV valve is not sealed and due for the full load test and tripping speed checked. Re-inspection required | 4/30/2025 | |
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A copy of the current state operating certificate shall be displayed in the machine room | 1/28/2025 | ||
MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | A copy of the current state operating certificate shall be displayed in the machine room | 6/3/2025 |