Inspection
Inspection Details
Equipment ID
19899
19899
Inspection Date
10/1/2018
10/1/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Wayne Ingram
Wayne Ingram
Mechanic Name
Kevin Crossland
Kevin Crossland
Relief Valve Pressure
300
300
Slide
Governor Rope Pull
Door Closing Force
20
20
External ID
b6173a0e-2e34-4bd7-af71-192b08156834
b6173a0e-2e34-4bd7-af71-192b08156834
Location
Valley Center Bldg #4
215 W MILL ST, SPRINGFIELD, MO
215 W MILL ST, SPRINGFIELD, MO
Owner
Brick City
PO BOX 9123, SPRINGFIELD, MO 65801-9123
PO BOX 9123, SPRINGFIELD, MO 65801-9123
Billing
Attn: Brick City
440 N CAMPBELL AVE, SPRINGFIELD, MO 65806-1259
440 N CAMPBELL AVE, SPRINGFIELD, MO 65806-1259
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | 1.18.1: Car Door restrictor shall work. (REINSPECTION WITHIN 30 DAYS) | 1/22/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.3 Guards Between Adjacent Pits | No | No | Pit shall be kept dry. Remove rust from pit channels, repaint, repair water leak. | 1/25/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.18 - Restricted opening of car or hoistway doors | 2.12.5 Restricted Opening of Hoistway or Car Doors (Re-Inspection) | Yes | No | 1.18.1: Car Door restrictor shall work. (REINSPECTION WITHIN 30 DAYS) | 1/22/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.3 Guards Between Adjacent Pits | No | No | Pit shall be kept dry. Remove rust from pit channels, repaint, repair water leak. | 1/22/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | G/2.7.1/8.6.1.6.5: Machine Room Fire Extinguisher shall have current monthly/annual test tag. No tag | 9/23/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | Permanently mount telephone line/flex to wall per NEC code | 9/23/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | ALARM BELL SHALL WORK WITH LOSS OF MAIN 120v POWER (REINSPECTION => 30days) (broken button) | 10/31/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine Room Fire Extinguisher shall have current monthly/annual test tag, no date present. (4lb ABC, replace with appropriate) | 11/22/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Lamps(overhead Cab lighting) shall be guarded. Missing ceiling panels. | 11/22/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Repair sump pump, spraying pit equipment, clean pit, remove rust from piping/jack. Repaint to reduce future rusting. Monitor for leaks. | 11/22/2022 |