Inspection
Inspection Details
Equipment ID
10905
10905
Inspection Date
2/3/2023
2/3/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas Sharp
Thomas Sharp
Mechanic Name
David Howerton
David Howerton
Relief Valve Pressure
420
420
Slide
Governor Rope Pull
Door Closing Force
16
16
External ID
3352bed2-251c-47e5-9925-58bbfcf826dd
3352bed2-251c-47e5-9925-58bbfcf826dd
Location
Ali-Dav Inc
1624 Delmar Blvd, St. Louis, MO
Phone: (314) 910-1717
1624 Delmar Blvd, St. Louis, MO
Phone: (314) 910-1717
Owner
Attn: Ali-Dav Inc
Ali-Dav Inc
10000 Watson Rd, Ste L5, St. Louis, MO 63126
Phone: (314) 822-1790
Email: crestwoodmed@yahoo.com
Ali-Dav Inc
10000 Watson Rd, Ste L5, St. Louis, MO 63126
Phone: (314) 822-1790
Email: crestwoodmed@yahoo.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The elevator machine and control equipment shall be located in a separate room designed as an elevator machine room and shall be accessible only to authorized personnel. No equipment shall be added to the machine room or space that is not used in connection with the operation of the elevator. It appears that the elevator machine room may have been altered and is no longer conforming to this requirement. | 8/4/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)9 | No | No | There is no protection found on this elevator power supply to prevent accidental motor phase reversal. Without a motor phase reversal device, there is a greater potential for equipment damage when a power loss occurs. Provide a motor phase reversal device on the elevator power supply. | 8/4/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | There shall be maintenance records kept in the elevator machine room or accessible to the inspector depicting dates and descriptions of maintenance tasks performed, callbacks, examinations, tests, adjustments, replacements and wiring diagrams. | 8/4/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher in the machine room does not have a current service tag and is not properly secured as required. Provide an ABC type extinguisher with a current service tag. | 8/4/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | The position indicating or “PI” device in the car was not operational on the day of inspection. Repair “PI” device to indicate the position of the elevator car. | 8/4/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | The current state operating certificate needs to be posted in the machine room in a non-combustible frame. | 8/4/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Expired | 8/4/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | None. | 8/4/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | Unsealed | 8/4/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | Tank/ controller located in cubby of hallway. Provide code compliant machine room. | 8/4/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Expired. | 8/4/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | 3rd floor braille/tactile plates have been painted, replace. | 8/4/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell does not work. | 4/29/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | The fire extinguisher is expired. | 4/29/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)9 | Yes | No | There is no protection found on this elevator power supply to prevent accidental motor phase reversal. Without a motor phase reversal device, there is a greater potential for equipment damage when a power loss occurs. Provide a motor phase reversal device on the elevator power supply. PREVIOUSLY CITED | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Repair damaged in-car emergency light. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | No | The position indicating or “PI” device in the car was not operational on the day of inspection. Repair “PI” device to indicate the position of the elevator car. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Machine Room shall have a properly mounted Fire Extinguisher, have current monthly/annual test tag. | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. | |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | Yes | No | 3rd floor braille/tactile plates have been painted, replace. PREVIOUSLY CITED |