Inspection
Inspection Details
Equipment ID
1165
1165
Inspection Date
2/1/2023
2/1/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Dixon Liljegren
Dixon Liljegren
Mechanic Name
Clinton Severs
Clinton Severs
Relief Valve Pressure
380
380
Slide
Governor Rope Pull
Door Closing Force
24
24
External ID
6eaaf9b9-f0a5-45c2-b819-c02581d633e5
6eaaf9b9-f0a5-45c2-b819-c02581d633e5
Location
Truman Building
301 W High St, Jefferson City, MO
Phone: (573) 571-7830
Email: mitchell.rogge@oa.mo.gov
301 W High St, Jefferson City, MO
Phone: (573) 571-7830
Email: mitchell.rogge@oa.mo.gov
Owner
Attn: INTERAGENCY
State of Missouri- Truman Bldg-INTERAGENCY
301 W High St, Ste 730, Jefferson City, MO 65101
Phone: (573) 751-0920
State of Missouri- Truman Bldg-INTERAGENCY
301 W High St, Ste 730, Jefferson City, MO 65101
Phone: (573) 751-0920
Billing
Attn: INTERAGENCY
OA- FMDC-HST RM 730-INTERAGENCY
PO Box 809, Jefferson City, MO 65102
Phone: (573) 751-0920
OA- FMDC-HST RM 730-INTERAGENCY
PO Box 809, Jefferson City, MO 65102
Phone: (573) 751-0920
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone not working. | 1/29/2020 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | Drip pan below pumping unit full, and overflowing onto machine room floor. | 5/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Fire service plackards missing/damaged at each landing. | 5/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Provide a type ABC fire extinguishere in machine room. | 5/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Provide MCP in machine room. | 5/15/2024 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current operating certificate in machine room. | 5/15/2024 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)2 | Yes | No | Top directional limit not working. | 2/1/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | COP floors 3 & 4 have key switches for security, and not accessible on FFS. | 2/1/2023 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone working, but not identifying location. | 2/1/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Provide a type ABC fire extinguisher in machine room. | 5/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide an MCP in machine room to log maintenance, repairs, and inspections. | 5/15/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | COP on floors 3 & 4 have key switches and are not accessible on FFS II. | 3/1/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone working, but not identifying the location. | 3/1/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | COP floors 3 & 4 are key access only, not accessible on FFS without a key. | 9/11/2024 |