Inspection
Inspection Details
Equipment ID
12523
12523
Inspection Date
2/6/2023
2/6/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Brenton Lane
Brenton Lane
Relief Valve Pressure
390
390
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
20
20
External ID
cb1a5c36-8965-4502-97fd-308444798e8c
cb1a5c36-8965-4502-97fd-308444798e8c
Location
Forest Park Community College
5600 Oakland Ave, St. Louis, MO
Phone: (314) 644-9151
5600 Oakland Ave, St. Louis, MO
Phone: (314) 644-9151
Owner
Attn: John Duarte
St. Louis Community College
3221 McKelvey Rd, Ste 100, Bridgeton, MO 63044
Phone: (314) 435-9505
Email: jduarte@stlcc.edu
St. Louis Community College
3221 McKelvey Rd, Ste 100, Bridgeton, MO 63044
Phone: (314) 435-9505
Email: jduarte@stlcc.edu
Billing
Attn: Accts payable
St. Louis Community College
3221 McKelvey Rd, Ste 100, Bridgeton, MO 63044
Phone: (314) 539-5263
Email: apayable@stlcc.edu
St. Louis Community College
3221 McKelvey Rd, Ste 100, Bridgeton, MO 63044
Phone: (314) 539-5263
Email: apayable@stlcc.edu
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | No | No | A fire extinguisher is required in the machine room. | 1/30/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.11.2.1.1(e) Car Lighting | No | No | The emergency light shall work. | 1/30/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display the current state operating certificate in the machine room. | 1/30/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 3/30/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 8.11.2.1.3(p) | No | No | Seal all penetrations in the hoistway. | 3/30/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/16/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 3/30/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.3.1.2(c) | No | No | The machine room lighting shall provided a minimum of 10 foot-candles at the floor. | 3/16/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency phone is not working. | 5/5/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | Fire extinguisher is expired. | 6/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No certificate posted in the machine room. | 6/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | There is no fire extinguisher. A current tested and tagged ABC type fire extinguisher shall be provided in the machine room. | 5/5/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 5/5/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | The pit light shall be operational. | 2/9/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 2/9/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 2/9/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | A current ABC type fire extinguisher shall be provided in the machine room. | 2/9/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 2/9/2026 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | No | No | Pit shall have code compliant lighting. | 2/9/2026 |