Inspection
Inspection Details
Equipment ID
12534
12534
Inspection Date
2/8/2023
2/8/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Cynthia "CJ" Brady
Cynthia "CJ" Brady
Mechanic Name
Brenton Lane
Brenton Lane
Relief Valve Pressure
300
300
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
19F/17R
19F/17R
External ID
5712709f-f3f5-4128-b31c-b70d85979e2d
5712709f-f3f5-4128-b31c-b70d85979e2d
Location
Forest Park Community College
5600 Oakland Ave, St. Louis, MO
Phone: (314) 644-9151
5600 Oakland Ave, St. Louis, MO
Phone: (314) 644-9151
Owner
Attn: John Duarte
St. Louis Community College
3221 McKelvey Rd, Ste 100, Bridgeton, MO 63044
Phone: (314) 435-9505
Email: jduarte@stlcc.edu
St. Louis Community College
3221 McKelvey Rd, Ste 100, Bridgeton, MO 63044
Phone: (314) 435-9505
Email: jduarte@stlcc.edu
Billing
Attn: Accts payable
St. Louis Community College
3221 McKelvey Rd, Ste 100, Bridgeton, MO 63044
Phone: (314) 539-5263
Email: apayable@stlcc.edu
St. Louis Community College
3221 McKelvey Rd, Ste 100, Bridgeton, MO 63044
Phone: (314) 539-5263
Email: apayable@stlcc.edu
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Fire service phase 2 car call cancel does not work and shall be repaired and tested. | 2/25/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency bell shall work. | 2/13/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.11.2.1.1(e) Car Lighting | No | No | The emergency lights shall work. | 3/5/2019 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.11.2.1.2(g) | No | No | A fire extinguisher is required in the machine room and the extinguisher shall not be expired. | 3/5/2019 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 3/30/2022 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | Yes | Yes | Fire Service Phase 1 & 2 are not working - Elevator Red Tagged - Elevator re-inspected on 2/4/2021 | 2/4/2021 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be displayed in the elevator machine room. | 3/16/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.1 - Access to machine space | 8.11.2.1.2(a) | No | No | The machine room door shall be self-closing. | 3/16/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. | 2/8/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | The in car emergency light shall be operational. | 2/8/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in car emergency telephone shall be operational. (2nd Notice) | 6/13/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | The fire extinguisher is expired. | 6/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No certificate in the machine room. | 6/21/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.5 - Car lighting and receptacles | 8.6.4.15 Emergency Lighting | Yes | No | The in car emergency light shall be operational. (2nd Notice) | 6/13/2023 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing | No | No | The overspeed valve is not sealed. It shall be tested with the rated load on or before the next annual test per MO AHJ. | 9/29/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in-car alarm bell shall be operational on main and on auxiliary power. | 1/29/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | No | On cars with two entrances, if both entrances can be opened on the designated level, only the doors serving the lobby where the "fire recall" switch is located shall open and remain open. Note: The top side entrance and car call has been rendered inoperative. The hall door shall be bolted shut. The door tries to open on phase one fire service and cannot because the hall door rollers have been removed and the restrictor is preventing it from opening. The door shall not attempt to open on phase one fire service. | 1/29/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.11.2.2.6 Fire Fighters Operation (Re-Inspection) | Yes | No | On cars with two entrances, if both entrances can be opened on the designated level, only the doors serving the lobby where the "fire recall" switch is located shall open and remain open. Note: The top side entrance and car call has been rendered inoperative. The hall door shall be bolted shut. The door tries to open on phase one fire service and cannot because the hall door rollers have been removed and the restrictor is preventing it from opening. The door shall not attempt to open on phase one fire service. | 6/12/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | The in-car alarm bell shall be operational on main and on auxiliary power. | 6/12/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be displayed in the machine room. | 8/6/2025 |
| A17.1-2016 : Elevators | 2.6 - Ventilation | 2.7.9.2 | Yes | No | Provide machine room ventilation to meet OEM temperature/humidity requirements. Can be natural or mechanical means. Shall maintain machine space fire rating. | 8/21/2025 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Yes | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 8/21/2025 |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4.1 | Yes | No | Machine room lighting disconnect shall have proper sized fusing (15A, not 20A). | 8/21/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | Overspeed valve was removed during alteration. This is required in Seismic Zone Building Code and shall be reinstalled and tested. | 8/21/2025 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Yes | No | An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. | 9/29/2025 |
| A17.1-2016 : Elevators | 2.6 - Ventilation | 2.7.9.2 | Yes | No | Provide machine room ventilation to meet OEM temperature/humidity requirements. Can be natural or mechanical means. Shall maintain machine space fire rating. | 9/29/2025 |