Inspection
Inspection Details
Equipment ID
14020
14020
Inspection Date
2/17/2023
2/17/2023
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
Slide
30”
30”
Governor Rope Pull
150/800
150/800
Door Closing Force
15
15
External ID
3779929a-914d-4dc4-a2e9-2c9b4ec73dab
3779929a-914d-4dc4-a2e9-2c9b4ec73dab
Location
AT & T- Data Center
801 Chestnut St, St. Louis, MO
Phone: (314) 235-9992
801 Chestnut St, St. Louis, MO
Phone: (314) 235-9992
Owner
Attn: AT&T Certificate Mgmt
AT&T Certificate Mgmt
9780 S Meridian Blvd, Ste 450, Englewood, CO 80112
Phone: (720) 874-5398
Email: att.elevators@lerchbates.com
AT&T Certificate Mgmt
9780 S Meridian Blvd, Ste 450, Englewood, CO 80112
Phone: (720) 874-5398
Email: att.elevators@lerchbates.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Fire service to be tested at a later date. | 8/19/2018 |
| conversion | conversion | conversion - reinspect | Yes | No | Emergency light not working on battery backup | 8/19/2018 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Alarm bell inoperative. | 7/15/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency light inoperative. | 2/5/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Written maintenance control program shall be kept on site. | 1/13/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Light in elevator pit is not working, needs repair | 1/13/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide testing of elevator on emergency power. | 4/20/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Provide testing of elevator emergency power selector switches (2). One at guard desk, one in fire control room. | 4/20/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Provide testing of Phase I operations, record results. | 4/20/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Provide testing of Phase II operations, record results. | 4/20/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Post current state elevator certificate. | 11/29/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | Hoist ropes need to be shortened | 5/30/2025 |
| MO Minimum : Elevators | (D) - Brakes | (D)2 | Yes | Yes | The pin that supports the brake pad on the machine has moved and needs to be repaired. Red-tagged, Re-inspection required | 5/30/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.11 Runby (Re-Inspection) | Yes | No | Hoist ropes need to be shortened. Re-inspection required | 1/13/2026 |
| MO Minimum : Elevators | (I) - Pits | (I)6 (Pit Lighting) | No | No | Light in elevator pit is not working, needs repair | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Need to test elevator for operation on emergency power. Re-inspection required |