Inspection
Inspection Details
Equipment ID
14841
14841
Inspection Date
2/15/2023
2/15/2023
Inspection Type
Major Alteration
Major Alteration
Inspector Name
David Folkert
David Folkert
Mechanic Name
Daniel Haymond
Daniel Haymond
Relief Valve Pressure
Na
Na
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
Na
Na
External ID
d8673774-48f1-49e5-9be2-81193757c948
d8673774-48f1-49e5-9be2-81193757c948
Location
Iatan Power Plant
20250 State Rte 45 N, Weston, MO
Phone: (816) 640-3661
Alt Phone: (816) 640-3661
Email: lynette.hurst@evergy.com
20250 State Rte 45 N, Weston, MO
Phone: (816) 640-3661
Alt Phone: (816) 640-3661
Email: lynette.hurst@evergy.com
Owner
Attn: Kevin Cook
KC Power & Light
1201 Walnut, Kansas City, MO 64141
Phone: (000) 000-0000
Email: kevin.cook@evergy.com
KC Power & Light
1201 Walnut, Kansas City, MO 64141
Phone: (000) 000-0000
Email: kevin.cook@evergy.com
Billing
Attn: Steven Thomas
Iatan Power Plant
20250 State Rte 45 N, Weston, MO 64098
Phone: (816) 640-3675
Email: steven.d.thomas@evergy.com
Iatan Power Plant
20250 State Rte 45 N, Weston, MO 64098
Phone: (816) 640-3675
Email: steven.d.thomas@evergy.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Replace hoistway gates that are corroded through the gate frame. | 8/11/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Door Systems 8.6.4.13 (Re-Inspection) | Yes | No | Replace car gates that are corroded through gate frame | 8/11/2021 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Replace electrical junction box mounted mid tower. Corrosion has exposed wiring inside the box | 8/5/2025 |
| MO Minimum : Elevators | (F) - Electrical Switches | (F)9 | No | No | Replace mainline disconnect. Disconnect can not be opened. | 8/5/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | no current operating cirt. | 8/5/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | missing backup roller on stile . | 8/5/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | tower mast cross bracing rusted thru in places | 8/5/2025 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)2 | No | No | rusty car top rusty angles holding up car top | 8/5/2025 |
| MO Minimum : Elevators | (K) - Car Platforms and Car Slings | (K)1 | No | No | underside of platform rusted | 8/5/2025 |
| MO Minimum : Elevators | (I) - Pits | (I)7 | No | No | pit access sw not working | 8/5/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | no MCP on site | 8/5/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.11.1.4(b)(1) Electric elevators Placed out of Service | Yes | Yes | elevator red tagged out of serv. for missing part an rust issuses on car an tower | 2/15/2023 |
| MO Minimum : Elevators | (D) - Brakes | (D)1 | Yes | Yes | The emergency brake release is not working. | 5/18/2026 |
| MO Minimum : Elevators | (A) - Hoistways | (A)6 | Yes | No | Adjust the bottom hall door interlock. | 5/18/2026 |