Inspection
Inspection Details
Equipment ID
15116
15116
Inspection Date
2/23/2023
2/23/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
23
23
External ID
57ae2505-e16b-4cdb-8fd2-c0d20ae732ff
57ae2505-e16b-4cdb-8fd2-c0d20ae732ff
Location
Hilton Hotel- STL
408 Olive St, St. Louis, MO
Phone: (000) 000-0000
408 Olive St, St. Louis, MO
Phone: (000) 000-0000
Owner
Attn: APHM St. Louis LLC
APHM St. Louis LLC
8910 University Blvd, Orlando, FL 32817
Phone: (000) 000-0000
APHM St. Louis LLC
8910 University Blvd, Orlando, FL 32817
Phone: (000) 000-0000
Billing
Attn: Hilton Hotel- STL Downtown ath the Arch
Hilton Hotel- STL Downtown ath the Arch
408 Olive St, St. Louis, MO 63102
Phone: (000) 000-0000
Email: vernon.matthews@hilton.com
Hilton Hotel- STL Downtown ath the Arch
408 Olive St, St. Louis, MO 63102
Phone: (000) 000-0000
Email: vernon.matthews@hilton.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Repair car flooring at entrance. Tripping hazard | 11/2/2018 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | No | No | Repair car floor tripping hazard | 6/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Clean pit | 6/15/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Replace hoist belts- rouging | 2/23/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service and document on log in machine room | 6/15/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Provide lighting in machine space top of hoistway | 6/15/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Replace volume on phone | 2/23/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing handrail | 6/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Remove excess lint from seismic wires in hoistway | 6/15/2024 |
| A17.1-2016 : Elevators | 1.12 - Car enclosure | 2.14.2.1 | No | No | Repair cover in car operating panel | 6/15/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)10 Car Floors | No | No | Repair car floor, repair cover in car operating panel item | 6/15/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | clean pit | 6/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Remove excess lint from seismic wires in hoistway | 6/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean car top | 6/15/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Provide lighting in machine space top of hoistway | 6/15/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Provide monthly fire service testing and document on log in machine room | 6/15/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | Increrase volumn on phone | 1/18/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing handrail in car | 6/15/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Mrl belts, repair car floor(tripping hazard), repair cover in car operating panel, clean pitm remove excess lint from seismic wiring in hoistway, clean car top. all of these violations were written up on last years inspection with no corrections made therefoe a 30 day maximum reinspcetion on all items. | 6/15/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | provide lighting in machine room space top hoistway | 6/15/2024 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | increase volumn on phone | 2/21/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Replace missing handrail in car | 6/15/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Reinspection for lighting in machine space top of hoistway checked and building management is currently getting a bid to have lighting installed. 30 day extension has been granted from date of this letter. | 6/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Reinspection for replacing missing handrail in car checked and failed needs to be reinspected | 6/15/2024 |
| A17.1-1996 : Elevators | 1.6 - Car emergency signal | 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | REPAIR THE PHONE IN THE CAR. REINSPECTION REQ WITHIN 30 DAYS. | 12/12/2025 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.11.2.1.5(a) | No | No | REPAIR THE PLIT LIGHT | 12/12/2025 |
| A17.1-2016 : Elevators | 6.1 - Operation of elevators under fire and other emergency conditions (A17.1b-1973 through A17.1b-1980) | 8.6.11.1 Firefighters’ Emergency Operation | No | No | PERFORM MONTHLY FIRE SERVICE TEST AND DOCUMENT ON THE LOG POSTED IN THE MACHINE ROOM | 12/12/2025 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | POST CURRENT STATE CERTIFICATE IN THE MACHINE ROOM | 12/12/2025 |