Inspection
Inspection Details
Equipment ID
15115
15115
Inspection Date
2/23/2023
2/23/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Steven Salabay
Steven Salabay
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
19
19
External ID
defdc9a0-1141-45ae-82e5-c91fc1d98796
defdc9a0-1141-45ae-82e5-c91fc1d98796
Location
Hilton Hotel- STL
408 Olive St, St. Louis, MO
Phone: (000) 000-0000
408 Olive St, St. Louis, MO
Phone: (000) 000-0000
Owner
Attn: APHM St. Louis LLC
APHM St. Louis LLC
8910 University Blvd, Orlando, FL 32817
Phone: (000) 000-0000
APHM St. Louis LLC
8910 University Blvd, Orlando, FL 32817
Phone: (000) 000-0000
Billing
Attn: Hilton Hotel- STL Downtown ath the Arch
Hilton Hotel- STL Downtown ath the Arch
408 Olive St, St. Louis, MO 63102
Phone: (000) 000-0000
Email: vernon.matthews@hilton.com
Hilton Hotel- STL Downtown ath the Arch
408 Olive St, St. Louis, MO 63102
Phone: (000) 000-0000
Email: vernon.matthews@hilton.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean pit | 6/15/2024 |
| A17.1-2016 : Elevators | 3.10 - Hoistway construction | 8.6.4.7 Cleaning of Hoistways | No | No | Remove excess lint from seismic wires 2.1.1.1.1 | 6/15/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Replace hoist belts - rouging | 2/23/2023 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service and document on log in machine room | 6/15/2024 |
| A17.1-2016 : Elevators | 2.4 - Machine space | 8.6.4.8 Machine Room and Machinery Space | No | No | Provide lighting in machine space top of hoistway 2.7.6.3.2(c) | 6/15/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean Pit | 6/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Remove excess lint from seismic wires in the hoistway | 6/15/2024 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Replace hoist belts (red rouge) WITHIN 30 DAYS | 1/18/2024 |
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | No | No | Perform monthly fire service and document on log in machine room | 6/15/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Provide lighting in machine space top of hoistway | 6/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | Clean car top | 6/15/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | MRL belts, clean pit where written up on last years inspections and no action has been taken 30 day maximum to correct these violations. | 6/15/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.7 Cleaning of Hoistway and Pit | No | No | Remove excess lint from seismic wires in the hoistway | 6/15/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Provide lighting in machine room space top of hoistway | 6/15/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Lighting at top of hoistway failed. Reinspection is required. Building management is currently getting bids for lighting at top of the hoistway and extension has been granted for 30 days as of the date of this report. | 6/15/2024 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters Emergency Operation: Monthly Testing | No | No | PERFORM MONTHLY FIRE SERVICE TEST AND DOCUMENT ON THE LOG POSTED IN THE MACHINE ROOM | 8/22/2025 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | POST CURRENT STATE CERTIFICATE IN THE MACHINE ROOM | 8/22/2025 |