Inspection
Inspection Details
Equipment ID
17341
17341
Inspection Date
2/24/2023
2/24/2023
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Michial Linenfelser
Michial Linenfelser
Mechanic Name
Brant Willtrout
Brant Willtrout
Relief Valve Pressure
600
600
Slide
Na
Na
Governor Rope Pull
Na
Na
Door Closing Force
19
19
External ID
b91a6c3d-b31b-4c3b-9363-8b4921361efd
b91a6c3d-b31b-4c3b-9363-8b4921361efd
Location
Materdie Place Condos
660 Materdie Ln # 664, Florissant, MO
Phone: (314) 420-9422
660 Materdie Ln # 664, Florissant, MO
Phone: (314) 420-9422
Owner
Attn: Lynn Porter
Materdie North Condo Association
660 Materdie Ln, Unit 303, Florissant, MO 63031
Phone: (618) 978-4790
Email: inkykat@msn.com
Materdie North Condo Association
660 Materdie Ln, Unit 303, Florissant, MO 63031
Phone: (618) 978-4790
Email: inkykat@msn.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | n/a | No | No | Machine Room not to be used for storage of non elevator related items. | 5/19/2020 |
| A17.1-1996 : Elevators | 2.1 - Access to machine space | 101.3a | No | No | Post current State certificate in machine room 5.100(2) | 5/19/2020 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | Remove all non elevator storage from machine room | 5/19/2020 |
| A17.1-1996 : Elevators | 2.6 - Ventilation | 1001.2(b)(6) | No | No | Repair machine room ventilation (fan) | 5/19/2020 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | Fire extinguisher is outdated as of 2011 | 5/19/2020 |
| A17.1-1996 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display updated certificate in machine room. | 5/19/2020 |
| A17.1-2016 : Elevators | 5.15.2 Unsealed Overspeed Valve | 8.6.5.16.5 (Re-Inspect) | Yes | No | OSV in pit is not sealed. Provide testing, tag and seal upon completion. 90 day compliance. | 2/24/2023 |
| A17.1-1996 : Elevators | 3.4 - Top-of-car Clearance, Refuge Space, & Standard Railing | 1206.2(c) | No | No | Clean car top. | 11/19/2025 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 1206.2a (Pits and Hoistways) | No | No | Clean pit. | 11/19/2025 |
| A17.1-1996 : Elevators | 2.7 - Fire Extinguisher | 1001.2(b)(7) | No | No | Service or replace fire extinguisher in machine room. | 11/19/2025 |
| A17.1-1996 : Elevators | 2.5 - Housekeeping | 1001.2(b)(5) | No | No | Clean machine room. | 11/19/2025 |
| A17.1-1996 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 106.1e Illumination of Pits | No | No | Pit light does not work. | 11/19/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | OSV in pit is not sealed. Perform OSV test, tag and seal upon completion. 30 day compliance. The original violation was noted on 7/21 inspection report. | 11/19/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | Service or replace fire extinguisher in elevator machine room. Noted on 7/21 report. | 11/19/2025 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | The elevator machine room shall be cleaned of dust and debris. Noted on 7/21 inspection report. | 11/19/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | The testing has not been completed on the elevator at this time. The weight test shall be performed, and the overspeed valve tested before the inspection is completed. | 11/19/2025 |