MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Two way communication is not working. Re-inspection required
|
2/10/2023
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
2/13/2024
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Unable to perform the following tests at this time: Set safeties with full load full speed, car buffer full load full speed, counterweight buffer, unintended car motion down direction, unintended car motion up direction, main brake, emergency brake, 125% capacity lower & hold. All items need to be performed to complete inspection. Re-inspection required
|
6/16/2023
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
x
|
Elevator failed 125% brake test. Elevator red-tagged and removed from service. Re-inspection required
|
10/25/2023
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Elevator would not run on emergency power. Re-inspection required
|
10/25/2023
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Previous violations that still need to be corrected are as follows: Test car safeties with rated load at rated speed, Test car buffer at rated speed with rated load, Test counterweight buffer at rated speed, Test unintended movement with full load in down direction and with no load in the up direction. Re-inspection required
|
10/25/2023
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Previous violations that still need to be corrected are as follows: Test car safeties with rated load at rated speed. Test car buffer at rated speed with rated load. Tast counterweight buffer at rated speed. Reinspect by 11/30/23
|
2/14/2024
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Elevator would not run on emergency power. Reinspect by 11/30/23
|
2/14/2024
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Elevator still hasn't been tested for operation on emergency power. Re-inspection required
|
7/3/2024
|