Inspection
Inspection Details
Equipment ID
14022
14022
Inspection Date
2/21/2023
2/21/2023
Inspection Type
5 Year Annual Inspection
5 Year Annual Inspection
Inspector Name
Michael Gallaher
Michael Gallaher
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
100 / 850
100 / 850
Door Closing Force
20
20
External ID
9cb8cc9a-4b41-42b7-891d-7cd656c7cc2a
9cb8cc9a-4b41-42b7-891d-7cd656c7cc2a
Location
AT & T- Data Center
801 Chestnut St, St. Louis, MO
Phone: (314) 235-9992
801 Chestnut St, St. Louis, MO
Phone: (314) 235-9992
Owner
Attn: AT&T Certificate Mgmt
AT&T Certificate Mgmt
9780 S Meridian Blvd, Ste 450, Englewood, CO 80112
Phone: (720) 874-5398
Email: att.elevators@lerchbates.com
AT&T Certificate Mgmt
9780 S Meridian Blvd, Ste 450, Englewood, CO 80112
Phone: (720) 874-5398
Email: att.elevators@lerchbates.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) | Yes | No | Alarm bell inoperative. | 10/10/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.1 General Maintenance Requirements Documentation | No | No | Written maintenance control program shall be kept on site. | 1/13/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Door close chicklets are missing on both in car operating panels, replace same. | 1/13/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 1/13/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.3.1 Replacement Parts | No | No | Door close chicklets are missing on both in car operating panels, need to be replaced | 1/13/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Test incomplete, need to perform full load full speed safeties, full load car buffer, counterweight buffer, 125% brake, emergency light/alarm, emergency phone & fire service tests. Re-inspection required | 3/28/2023 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevator shall be tested on emergency power | 4/20/2023 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate needs to be properly displayed in machine room | 1/13/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Door close chicklets are missing on both in car operating panels. | 1/13/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency power shall be tested for 2024. Re-inspection required | 4/14/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 1/13/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room | 1/13/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency power shall be tested for 2024. Re-inspection required | 1/13/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Door close chicklets are missing on both in car operating panels, replace same. | |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency power shall be tested for 2024. Re-inspection required | |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A copy of the current state operating certificate shall be displayed in the machine room |