Inspection
Inspection Details
Equipment ID
7121
7121
Inspection Date
2/15/2023
2/15/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Jeff Setchfield
Jeff Setchfield
Relief Valve Pressure
460
460
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
23
23
External ID
5eef0789-9b27-4d53-ba38-7a9731399ac0
5eef0789-9b27-4d53-ba38-7a9731399ac0
Location
Parkwood Skilled & Rehab Ctr
3201 Parkwood Ln, Maryland Heights, MO
Phone: (314) 291-5911
Email: JohnW@rileyspence.com
3201 Parkwood Ln, Maryland Heights, MO
Phone: (314) 291-5911
Email: JohnW@rileyspence.com
Owner
Attn: Riley Spence & Associates
Riley Spence & Associates
1749 Gilsinn Ln, Fenton, MO 63026
Phone: (000) 000-0000
Riley Spence & Associates
1749 Gilsinn Ln, Fenton, MO 63026
Phone: (000) 000-0000
Billing
Attn: Parkwood Skilled & Rehab Ctr
Riley Spence & Associates
3201 Parkwood Ln, Maryland Heights, MO 63043
Phone: (000) 000-0000
Email: slyerspauljc@yahoo.com
Riley Spence & Associates
3201 Parkwood Ln, Maryland Heights, MO 63043
Phone: (000) 000-0000
Email: slyerspauljc@yahoo.com
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | All the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 10/20/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | All the on site documentation required by A17.1 2016 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Note: Currently schematics, oil log, and maintenance log are present - please supply the MCP approved by the MO State AHJ. | 3/4/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO state operating certificate shall be posted in the elevator equipment shall be posted in the elevator equipment room in a noncombustible frame with a clear protective vision plate over it. | 3/4/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/4/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 11/18/2024 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | This unit is equipped with an unsealed overspeed valve and shall be tested with the rated load. This valve may have been installed 9/22 when an alteration (new pumping unit) was installed and inspected by St. Louis County. It is not sealed or tagged, and the adjustment locknut has not been locked down. The on-site MCP was just put in the machine room the day of the inspection, so there is no record of the OSV ever being tested. | 11/18/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.5 Code Data Plate | No | No | The code data plate shall be provided in plain view, securely attached to each main line disconnect or controller. | 3/4/2026 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | 8.6.5.16.5 Over Speed Valve Testing (Re-Inspect) | Yes | No | This unit is equipped with an unsealed overspeed valve and shall be tested with the rated load. This valve may have been installed 9/2022 when an alteration (new pumping unit) was installed and inspected by St. Louis County. It is not sealed or tagged, and the adjustment locknut has not been locked down. The on-site MCP was just put in the machine room the day of the inspection, so there is no record of the OSV ever being tested. Note: To date this testing has not been performed and customer has not approved elevator company to perform this testing. Failure to perform category 5 test of the overspeed valve within 90 days will result in the unit being locked out of service. | 6/20/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 6/20/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. (3rd Notice and Final Notice) Failure to test emergency generator may result in the unit being locked out of service until complete. | 3/4/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | Emergency lighting shall work. (1 of 2 lamps missing) | 3/4/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)1 | No | No | Means of access to machine space door shall be clear and unobstructed. Multiple mop and 5 gallon buckets blocking the door. | 3/4/2026 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)5 (Machine Room Lighting) | No | No | Machine room lighting shall work. One or more bulbs are not working. | 3/4/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2 On-Site Documentation | No | No | Compliant/required documentation & MCP shall be kept in equipment room (neat/organized and not on car top) including wiring diagrams, oil log, and fire service log, recorded monthly. | 3/4/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 3/4/2026 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | Code year data tag shall be installed on controller. | 3/18/2026 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Cab lighting - all lamps shall work. | 3/18/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Current State operating certificate shall be located in the machine room. | 3/18/2026 |