Inspection
Inspection Details
Equipment ID
5424
5424
Inspection Date
8/20/2018
8/20/2018
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Gary Beadle
Gary Beadle
Mechanic Name
Scott Breihan
Scott Breihan
Relief Valve Pressure
470
470
Slide
Governor Rope Pull
N/A
N/A
Door Closing Force
23
23
External ID
bd2aecf4-c6ab-4a41-a46f-d41c039d9ebe
bd2aecf4-c6ab-4a41-a46f-d41c039d9ebe
Location
Kirkwood Community Center
111 S GEYER RD, KIRKWOOD, MO
111 S GEYER RD, KIRKWOOD, MO
Owner
Kirkwood, City of
139 S KIRKWOOD RD, KIRKWOOD, MO 63122-4303
139 S KIRKWOOD RD, KIRKWOOD, MO 63122-4303
Billing
Attn: Kirkwood, City of
212 S TAYLOR AVE, KIRKWOOD, MO 63122-4325
212 S TAYLOR AVE, KIRKWOOD, MO 63122-4325
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) | Yes | No | The in car emergency telephone shall be operational. | 11/5/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 8/22/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. | 8/22/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6 General Maintenance Methods | No | No | The disconnect located in the machine room shall be provided with a sign to identify the location of the supply side overcurrent protective device. | 8/22/2022 |
| MO Minimum : Elevators | (S) - Fire Service | 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) | Yes | No | Did not have the key to test the stop switch device in Phase 1. | 8/4/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator machine room. | 9/15/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | The MCP, including PM records and monthly fire service test log, are not being properly documented. | 2/14/2024 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean. | 2/14/2024 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.8.2 | No | No | Machine Space shall have at least one(1) GFCI outlet. Currently no outlet available. Both positions take by building Cable modem and Elevator phone system. | |
| A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 8.10.2.2.2(r) | No | No | Mainline disconnect while not return to the closed position normally. Locking device is faulty |