Inspection
Inspection Details
Equipment ID
24513
24513
Inspection Date
3/1/2023
3/1/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Thomas McGrath
Thomas McGrath
Mechanic Name
John Palmer, Jr
John Palmer, Jr
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA/NA
NA/NA
Door Closing Force
20
20
External ID
28c51bca-6d4d-4725-a279-779051ad7b5f
28c51bca-6d4d-4725-a279-779051ad7b5f
Location
Aloft Hotels
4245 Duncan Ave, St. Louis, MO
Phone: (000) 000-0000
4245 Duncan Ave, St. Louis, MO
Phone: (000) 000-0000
Owner
Attn: Kathy Prainito
Midas Cortex, LLC
1804 Borman Circle Drive, St. Louis, MO 63146
Phone: (314) 991-1158
Email: KPrainito@midashospitality.com
Midas Cortex, LLC
1804 Borman Circle Drive, St. Louis, MO 63146
Phone: (314) 991-1158
Email: KPrainito@midashospitality.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.8 - Hoistway enclosure | 8.11.2.1.4(h) | x | Seal all penetrations in the hoistway. | 5/11/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.2-2.27.8 | x | x | All phases of fire service shall be tested. | 5/11/2020 |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump pump shall be provided | x | Finish the installation of the sump pump and cover. | 5/11/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.15 - sign and operating device symbols | 8.11.2.1.1(o) | x | Finish construction of the elevator lobby and mount all fixtures and signage. | 5/11/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.3 - Lighting and receptacles | 8.11.2.1.2(c) | x | Install lighting (19 ftc) in overhead machine space with switch and GFCI. | 5/11/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 Illumination of Pits | x | Install lighting (10 ftc) in the pit with switch and GFCI. | 5/11/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.4 - Sills and car floor | 8.11.2.1.1(d) | x | Finish the elevator floor. | 5/11/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.4 - Sills and car floor | 8.11.2.1.1(d) | x | Finish grouting the sills. | 5/11/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The emergency lighting and alarm shall be tested. | 5/11/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | Check for proper operation of the emergency phone. | 5/11/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.8 - Pipes, wiring, and ducts | 8.11.2.1.2(h) | x | Install all electrical covers. | 5/11/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.9 - Floor and emergency identification numbering | 2.29.2 | x | Number the hoistway doors. | 5/11/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4 | x | Label disconnects for feed source. | 5/11/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 4.5 - Access to Hoistway | 8.11.2.1.4(e) | x | Check hoistway access. | 5/11/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.11 - Hoistway smoke control | 2.1.4 | The powered hoistway vent in the overhead shall automatically open upon detection of smoke in the elevator lobbies or hoistway, and upon power failure. | 5/18/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.10 - Hoistway construction | 2.1 | The powered hoistway vent in the overhead shall be sealed with masonry or other approved solid materials. | 5/18/2020 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 2.3.2 | x | The counterweight guard must extend from the lowest part of the counterweight assembly when the counterweight is resting on the fully compressed buffer. | 5/18/2020 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | x | Emergency power operation of the elevators shall be tested. | 4/5/2021 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone shall be operational. | 4/5/2021 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.6 - Car emergency signal | 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | x | The in car emergency telephone is still not operational. | 6/23/2021 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 1.17 - Standby power operation | 8.11.2.1.1(q) | x | The emergency power indicator light shall illuminate to indicate the standby/emergency power is activated. The indicator light shall be operational and emergency power shall be tested. | 6/23/2021 | |
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 3.17 - Door and gate equipment | 2.11 | Install Missing fire stops on hoistway doors | 9/21/2022 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Install ABC Rated extinguisher on 5th floor in view of controller | 9/21/2022 | ||
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | Remove prints and maintenance records from top of car | 9/21/2022 | ||
| A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 8.6.11.1 Firefighters’ Emergency Operation Documentation | Perform monthly fire service test and document on log in machine room | 9/21/2022 | ||
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | Remove storage from the top of the car | 6/26/2023 | ||
| MO Minimum : Elevators | (S) - Fire Service | 8.6.11.1 Monthly Test and Log | Perform monthly fire service and document on log in machine room | 3/18/2024 | ||
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | Install a ABC Rated Fire Extinguisher on the 5th floor in sight of the elevator controls | 3/18/2024 | ||
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | Test emergency power operation | 3/20/2025 |