Inspection
Inspection Details
Equipment ID
16887
16887
Inspection Date
2/16/2023
2/16/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
Mitchell McNeely
Mitchell McNeely
Mechanic Name
Mark Brown
Mark Brown
Relief Valve Pressure
na
na
Slide
na
na
Governor Rope Pull
na
na
Door Closing Force
na
na
External ID
1bd3b1ab-c425-478a-9f8c-048c5ec34a5e
1bd3b1ab-c425-478a-9f8c-048c5ec34a5e
Location
St. Louis Busch Stadium
700 Clark Ave, St. Louis, MO
Phone: (314) 345-9404
Email: hbaker@cardinals.com
700 Clark Ave, St. Louis, MO
Phone: (314) 345-9404
Email: hbaker@cardinals.com
Owner
Attn: Hope Baker
St. Louis Cardinals LLC
700 Clark Ave, St. Louis, MO 63102
Phone: (314) 345-9309
Email: hbaker@cardinals.com
St. Louis Cardinals LLC
700 Clark Ave, St. Louis, MO 63102
Phone: (314) 345-9309
Email: hbaker@cardinals.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Comb impact guides are rusted and need to be tested to insure roper impact calibration. | 2/18/2019 |
| A17.1-1996 : Escalators | 7.7 - Combplate and comb step impact device | 807.3 | No | No | Comb impact guides are rusted. Pressure test on tripping pressure needed. Reinspect in 30 days. | 3/29/2023 |
| A17.1-1996 : Escalators | 7.3 - Handrails | 802.2 | No | No | Both handrails are cracked. | 7/12/2023 |
| A17.1-1996 : Escalators | 7.5 - Lighting | 805.7 | No | No | Lower demarcation lights do not work. | 7/12/2023 |
| A17.1-1996 : Escalators | 7.7 - Combplate and comb step impact device | 802.6 | No | No | Replace two broken step demarcations. | 7/12/2023 |
| A17.1-1996 : Escalators | 7.5 - Lighting | 805.7 | No | No | Demarcation light at the top landing does not work | 7/12/2023 |
| A17.1-2016 : Elevators | 7.17 - Step/skirt clearances, panels, and performance index | 8.6.8.3.3 | Yes | No | Step/skirt clearances exceeded the allowed amount of .25. | 7/21/2023 |
| A17.1-2016 : Elevators | 7.3 - Handrails | 8.6.8.1 | No | No | Right handrail is cracked and has possible pinching hazards. Replace handrail | 7/12/2023 |
| A17.1-2016 : Elevators | 7.17 - Step/skirt clearances, panels, and performance index | 8.6.8.3.3 | No | No | Step/skirt clearances exceeded the allowed amount of .25 on the upper right side. | 8/13/2024 |
| Missouri Minimum : Escalators | (T) - Existing Dumbwaiters, Escalators and Moving Walks | 8.6.8.2 Escalator Step-to-Skirt Clearance | Yes | No | Adjust right side skirt at top for proper clearence to pass the loaded gap and index testing | 8/13/2024 |
| A17.1-1996 : Escalators | 7.3 - Handrails | 802.2 | No | No | Replace left side handrail | 8/26/2025 |
| A17.1-1996 : Escalators | 7.3 - Handrails | 802.2 | No | No | Adjust handrail tension- both handrails | 8/26/2025 |
| A17.1-1996 : Escalators | 7.5 - Lighting | 806.2 | No | No | Provide lighting at upper end of unit per code. | 8/26/2025 |
| A17.1-2016 : Elevators | 9.19 - Maintenance Records | 8.6.1.4.1(b)(1) | No | No | On site maintenance records for call backs, repairs ,testing, & indexing to be on site and location of where they are located listed | 8/26/2025 |
| A17.1-2016 : Elevators | 2.5 - Housekeeping | 8.6.4.8 Machine Room and Machinery Space | No | No | Clean out lower end pit of escalator - leaves and Debris | 8/26/2025 |