Inspection
Inspection Details
Equipment ID
3694
3694
Inspection Date
2/21/2023
2/21/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
Curtis Belew
Curtis Belew
Mechanic Name
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
7b7ee1e4-ac21-4979-a769-ba43052189f8
7b7ee1e4-ac21-4979-a769-ba43052189f8
Location
Bel Aire Apartments
8330 Delcrest Dr, St. Louis, MO
Phone: (314) 994-7251
8330 Delcrest Dr, St. Louis, MO
Phone: (314) 994-7251
Owner
Attn: National Real Estate
National Real Estate
9986 Manchester Rd, St. Louis, MO 63122
Phone: (314) 878-5545
Email: bmelton@nremgmt.com
National Real Estate
9986 Manchester Rd, St. Louis, MO 63122
Phone: (314) 878-5545
Email: bmelton@nremgmt.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | Cab lights shall be guarded. | 5/12/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | 8.6.5.8 - Possible single bottom jack. Provide documentation that jack is not a single bottom type. | 5/12/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | 8.6.5.8 - Possible single bottom jack. Provide documentation that jack is not a single bottom type. | 5/12/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) | 12/14/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. | 9/2/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)2 | No | No | The machine room door shall be self-closing and self-locking. | 9/2/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | Display a current MO State operating certificate in the machine room. | 9/2/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Control prints are missing. | 9/2/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)5 | No | No | Where the depth of any pit is 4 feet or more it shall have a ladder permanently installed. The ladder shall extend not less then 30 inches above the sill of the access door, or hand grips shall be provided to the same height. The ladder shall be of noncombustible material. | 9/2/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)4 | Yes | No | All gates and doors shall comply to A17.1 - 1955, Rule 204.4 - The distance from the face of the hoistway door to the face of the car gate shall not exceed 4 inches. (Re-inspection required in 30 days) | 2/21/2023 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | The pit shall be kept clean and dry. Remove the water from the pit floor. Unable to observe OSV. | 5/17/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.5 Fire Extinguishers | No | No | A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. The fire extinguisher is expired. | 5/10/2024 |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 8.6.4.7 Cleaning of Pits | Yes | No | The pit shall be kept clean and dry. | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) | Yes | No | Sump pump is clogged and not pumping. | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.5 | Yes | No | The pit light shall illuminate when switch on. |