Inspection
Inspection Details
Equipment ID
217
217
Inspection Date
3/8/2023
3/8/2023
Inspection Type
Annual Inspection
Annual Inspection
Inspector Name
James VanZant
James VanZant
Mechanic Name
Benjamin Kurzava
Benjamin Kurzava
Relief Valve Pressure
NA
NA
Slide
1in
1in
Governor Rope Pull
75/450
75/450
Door Closing Force
21
21
External ID
8e1f66b3-be4c-488b-a80c-aa1feffc4e44
8e1f66b3-be4c-488b-a80c-aa1feffc4e44
Location
Heritage Towers
515 W MOUNT VERNON ST, SPRINGFIELD, MO
Phone: (417) 207-4888
515 W MOUNT VERNON ST, SPRINGFIELD, MO
Phone: (417) 207-4888
Owner
Attn: Chuck Hicks
Springfield Housing Authority
421 W Madison St, Springfield, MO 65806
Phone: (000) 000-0000
Email: chicks@hasproperties.org
Springfield Housing Authority
421 W Madison St, Springfield, MO 65806
Phone: (000) 000-0000
Email: chicks@hasproperties.org
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | 1/5/21:: 2-way communication device shall work and give proper location (REINSPECTION REQUIRED) | 8/11/2021 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | 2-way communication device shall work and give proper location (REINSPECTION REQUIRED) | 8/11/2021 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)8 | No | No | H(8). 4x4 electrical box (Phone wiring) in machine room needs to have wiring inside box and cover installed. | 3/31/2022 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)6 | No | No | H(6). Machinery, controllers, governors, disconnects shall be numbered conspicuously. | 3/31/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | TESTING INCOMPLETE. MUST RETURN TO COMPLETE. Required within 30days | 3/16/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | TESTING INCOMPLETE. MUST RETURN TO COMPLETE. Required within 30days | 3/16/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | B(11)/1.6.1/ : 2-way communication device shall work and give proper location (REINSPECTION 14days to REDTAG) | 3/31/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | TESTING INCOMPLETE. Fire Service and Door# be tested to complete. F.S. Keys needed | 3/31/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | B(11)/1.6.1/ : 2-way communication device shall work and give proper location (REINSPECTION 14days to REDTAG) | 3/31/2022 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (2)(C) Re-Inspection Required to Enforce. | Yes | No | TESTING INCOMPLETE. Fire Service and Door# be tested to complete. F.S. Keys needed | 3/31/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) | No | No | Provide MCP in machine room | 5/3/2024 |
| MO Minimum : Elevators | (H) - Machine Rooms | (H)4 | No | No | remove rubbish and material from machine room floor | 6/26/2025 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Replace the hoist ropes due to undersizing | 6/26/2025 |