Inspection
Inspection Details
Equipment ID
26102
26102
Inspection Date
3/8/2023
3/8/2023
Inspection Type
Temporary Certificate Inspection
Temporary Certificate Inspection
Inspector Name
Jerry Eckhart
Jerry Eckhart
Mechanic Name
Bobby Strader
Bobby Strader
Relief Valve Pressure
na
na
Slide
4
4
Governor Rope Pull
21 / 190
21 / 190
Door Closing Force
na / 21
na / 21
External ID
525bd0c8-dc47-4d42-8eb0-093c9e79c8ef
525bd0c8-dc47-4d42-8eb0-093c9e79c8ef
Location
Streets of St. Charles
333 Mulholland Dr, St. Charles, MO
Phone: (000) 000-0000
333 Mulholland Dr, St. Charles, MO
Phone: (000) 000-0000
Owner
Attn: Chapter at the Streets, LLC
Chapter at the Streets, LLC
333 Mulholland Dr, St. Charles, MO 63303
Phone: (000) 000-0000
Email: chart@brinkmannconstructors.com
Chapter at the Streets, LLC
333 Mulholland Dr, St. Charles, MO 63303
Phone: (000) 000-0000
Email: chart@brinkmannconstructors.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | Yes | No | Increase machine space illumination to 19 ft-candles minimum | 5/11/2023 |
| A17.1-2016 : Elevators | 2.3 - Lighting and receptacles | 2.7.9.1 | Yes | No | Increase machine space lighting to 19 ft-candles minimum | 5/11/2023 |
| A17.1-2016 : Elevators | 2.8 - Pipes, wiring, and ducts | 2.8.3 | Yes | No | Provide shunt trip for mainline. Activated by a heat detector | 5/11/2023 |
| A17.1-2016 : Elevators | 3.11 - Hoistway smoke control | 2.1.4 | Yes | No | Provide a means of smoke control in the hoistway compliant with the building code | 5/11/2023 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | The emergency/standby power shall be tested. | 8/27/2024 |
| A17.1-2016 : Elevators | 2.7 - Fire Extinguisher | 8.6.1.6.5 | No | No | An ABC fire extinguisher with a current test tag shall be mounted convient to the machine room door. | 12/3/2024 |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 2.7.6.3.4 | Yes | No | The remote governor tripping/reset means on the controller (means to test) shall be operational. | 8/27/2024 |
| A17.1-2016 : Elevators | 2.13 - Governor, Overspeed Switch, and Seal | 2.7.6.3.4 | Yes | No | The remote governor tripping/reset means on the controller (means to test) shall be operational. | 11/25/2024 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.2.1 Repair Parts | No | No | The emergency power jewel at main lobby does not illuminate when emergency power operation is enabled. | 12/3/2024 |
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 2.27.2 | Yes | No | Elevators equipped to operate on emergency power shall be tested with no load in the car, operating on emergency power annually. | 5/22/2025 |
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.2 On-Site Documentation | No | No | Compliant/required documentation shall be kept on-site including MCP wiring diagrams, PM log, callback log, and evacuation procedures. No such documentation on-site for 2023, 2024, and 2025. | 4/7/2026 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. | 4/7/2026 |
| A17.1-2016 : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | No State operating certificate in the machine room. | 5/6/2026 |