Inspection
Inspection Details
Equipment ID
10269
10269
Inspection Date
3/2/2023
3/2/2023
Inspection Type
Reinspection
Reinspection
Inspector Name
Christopher "RED" Staton
Christopher "RED" Staton
Mechanic Name
Richard King
Richard King
Relief Valve Pressure
NA
NA
Slide
NA
NA
Governor Rope Pull
NA
NA
Door Closing Force
NA
NA
External ID
df31c3bf-9eed-473b-90af-295536e68fa9
df31c3bf-9eed-473b-90af-295536e68fa9
Location
MO Baptist Medical Center
3015 N NEW BALLAS RD, ST. LOUIS, MO
Phone: (314) 996-5000
3015 N NEW BALLAS RD, ST. LOUIS, MO
Phone: (314) 996-5000
Owner
Attn: MO Baptist Medical Center
MO Baptist Medical Center
3015 N Ballas Rd, St. Louis, MO 63131
Phone: (314) 996-5412
Email: Laura.Bradbury@bjc.org
MO Baptist Medical Center
3015 N Ballas Rd, St. Louis, MO 63131
Phone: (314) 996-5412
Email: Laura.Bradbury@bjc.org
Billing
Attn: Brian Irvine
MO Baptist Medical Center
3015 N Ballas Rd, St. Louis, MO 63131
Phone: (314) 996-5412
Email: brian.irvine@bjc.org
MO Baptist Medical Center
3015 N Ballas Rd, St. Louis, MO 63131
Phone: (314) 996-5412
Email: brian.irvine@bjc.org
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| conversion | conversion | conversion - reinspect | Yes | No | Re-install the 6th floor hoistway dust cover. | 5/31/2019 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Clean the car top. | 3/17/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Provide numbering on car top. | 3/17/2022 |
| MO Minimum : Elevators | (I) - Pits | (I)1 | No | No | Clean the pit. | 3/17/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)8 Car Lighting | No | No | The emergency lights shall work. | 3/17/2022 |
| MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | Yes | No | The emergency bell shall work. | 5/14/2020 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Replace missing bottom door guide at the 5th floor hoistway door. | 3/17/2022 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 Maintenance, Repair and Replacements | No | No | Re-install the 6th floor hoistway dust cover. (Violation not cleared from previous annual inspection) | 3/17/2022 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)12 (Re- Inspection) | Yes | No | Replace the governor rope. Violation repaired on 9/21/2020 and scheduled for re-inspection on 10/5/2020 | 10/5/2020 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Fire service shall be tested. | 12/29/2021 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Emergency/standby power operation of the elevator shall be operational. | 12/29/2021 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | Provide a code compliant MCP including onsite documents. (This item is for notification purposes for future violation in 2022) | 3/17/2022 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 8/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. | 8/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1 - 8.6.4.13 - Door systems | Yes | No | The car door restrictor vane is missing on the 2nd floor hoistway door. | 3/2/2023 |
| MO Minimum : Elevators | (L) - Wire Ropes-Hoisting, Governor and Tiller | (L)1(A) | No | No | Install hoist rope data tags. | 8/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.6.7 Signs and Data Plates | No | No | The car numbering on the crosshead is incorrect. The proper elevator number shall be displayed on the crosshead. | 8/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency light and bell shall be operational. | 3/2/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency bell shall be operational. (2nd Notice) | 3/2/2023 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) | Yes | No | The in car emergency bell shall be operational on main and auxiliary power. (2nd Notice) | 6/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.7.2 Periodic Test Record (Test Tags) | No | No | Current test tags shall be installed on governor, safeties (releasing carrier), buffers, etc. | 8/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | No | No | A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. MCP shall be kept in machine room, not on car top. | 8/18/2025 |
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | No | No | A current MO State operating certificate shall be obtained and displayed in the elevator machine room. | 8/18/2025 |
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.4.9 Cleaning of Top of Cars | No | No | The car top shall be cleaned. | 8/18/2025 |
| MO Minimum : Elevators | (A) - Hoistways | (A)16 | No | No | Replace missing interlock covers in the hoistway. There are exposed live wires. | 8/18/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Fire service shall be tested. | 6/18/2025 |
| MO Minimum : Elevators | 11 CSR 40-5.090 Inspection and Testing | (3) Testing Procedures (Re-Inspect) | Yes | No | Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. | 6/18/2025 |