Inspection
Inspection Details
Equipment ID
17856
17856
Inspection Date
3/16/2023
3/16/2023
Inspection Type
Other Inspection
Other Inspection
Inspector Name
Ronald Edwards
Ronald Edwards
Mechanic Name
Gordon Willich
Gordon Willich
Relief Valve Pressure
n/a
n/a
Slide
28 ins.
28 ins.
Governor Rope Pull
520
520
Door Closing Force
27
27
External ID
e3dd1549-3642-4905-a358-2f35b12c4c6a
e3dd1549-3642-4905-a358-2f35b12c4c6a
Location
Independence Regional Health Center
19600 E 39th St S, Independence, MO
Phone: (816) 698-7000
19600 E 39th St S, Independence, MO
Phone: (816) 698-7000
Owner
Attn: Randall Murphy
Center Point Medical Center
19600 E 39th St S, Independence, MO 64057
Phone: (816) 698-7093
Email: randall.murphy@hcamidwest.com
Center Point Medical Center
19600 E 39th St S, Independence, MO 64057
Phone: (816) 698-7093
Email: randall.murphy@hcamidwest.com
Billing
Same as Owner
Violations
| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| MO Minimum : Elevators | (G) - Maintenance, Repair and Replacements | 8.6.1.4 Maintenance records | no maint records on site | 2/29/2024 | ||
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | emg power couldnt be tested at time of insp | 2/25/2021 | ||
| A17.1-2016 : Elevators | 2.17 - Drive machine brake | 8.7.2.25.1 | no rope gripper but new mach. | 2/25/2021 | ||
| A17.1-2016 : Elevators | 2.16 - Overhead Beam and Fastenings | 8.7.2.9 | no report from lic. pro. eng. on support for new floor an mach.room beams | 9/16/2024 | ||
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | standby power test didnt work properly | 2/25/2021 | ||
| A17.1-2016 : Elevators | 2.17 - Drive machine brake | 8.7.2.25.1 | no rope gripper or emg. brake | 2/25/2021 | ||
| A17.1-2016 : Elevators | 2.40 - Maintenance Records | 8.6.1.2.1(a) | no mcp on site | 2/29/2024 | ||
| A17.1-2016 : Elevators | 2.16 - Overhead Beam and Fastenings | 8.7.2.9 | no report by prof. eng. on machine room floor over hoistway | 9/16/2024 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | no current cirt. displayed | 9/16/2024 | ||
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | test couldnt be done at this time scheduled for april | 2/29/2024 | |
| A17.1-2016 : Elevators | 2.17 - Drive machine brake | 8.7.2.25 | x | emg. brake not installed as per code | 2/29/2024 | |
| A17.1-2016 : Elevators | 2.16 - Overhead Beam and Fastenings | 8.7.2.9 | no report on mach room floor by prof. eng. | 9/16/2024 | ||
| A17.1-2016 : Elevators | 4.1 - Car platform guard | 2.15.9 | platform guard less than 48 ins. | 9/16/2024 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | no current cirt displayed | 9/16/2024 | ||
| MO Minimum : Elevators | CSR 40-5.100 State Operating Certificate | 5.100(2) Display of Operating Certificate | no current cirt displayed | 9/16/2024 | ||
| A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.5.14.3(f) | x | emg power couldnt be tested at time of insp | 3/6/2024 | |
| A17.1-2016 : Elevators | 4.1 - Car platform guard | 2.15.9 | platform guard needs to be 48 ins or have a variance | 9/16/2024 | ||
| ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators | 5.2 - Bottom clearance, runby, and minimum refuge space | 8.6.4.11 | x | Zero counterweight runby, shorten ropes. |